Sanyo KHS2472 Air Conditioner User Manual


 
Indoor Unit : KHS1872
Outdoor Unit : CH1872
Power Supply : 230V Single Phase 60Hz
< Cooling Capacity >
5-2. Cooling Capacity
RATING CAPACITY: 17,500 BTU/h AIR FLOW RATE: 524 CFM
INDOOR OUTDOOR
ENT. TEMP.
o
F (
o
C)AMBIENT TEMP.
o
F (
o
C)
W.B. D.B. 65 75 85 95 105 115
(18.3) (23.9) (29.4) (35.0) (40.6) (46.1)
TC 17,710 17,180 16,600 16,040 15,320 10,530
72 (22.2) SHC 13,110 12,910 12,610 12,300 12,000 9,760
59 76 (24.4) SHC 14,840 14,640 14,340 14,030 13,720 10,530
(15.0) 80 (26.7) SHC 16,670 16,370 16,060 15,860 15,320 10,530
84 (28.9) SHC 17,710 17,180 16,600 16,040 15,320 10,530
88 (31.1) SHC 17,710 17,180 16,600 16,040 15,320 10,530
TC 18,460 17,920 17,330 16,770 16,040 10,770
72 (22.2) SHC 11,080 10,880 10,570 10,370 9,960 7,720
63 76 (24.4) SHC 12,810 12,610 12,300 12,000 11,6909,450
(17.2) 80 (26.7) SHC 14,640 14,340 14,130 13,830 13,520 10,770
84 (28.9) SHC 16,370 16,060 15,860 15,560 15,250 10,770
88 (31.1) SHC 18,100 17,790 17,330 16,770 16,040 10,770
TC 19,190 18,650 18,060 # 17,500 16,750 10,980
72 (22.2) SHC 9,050 8,740 8,540 8,330 8,030 5,790
67 76 (24.4) SHC 10,780 10,470 10,270 10,060 9,760 7,520
(19.4) 80 (26.7) SHC 12,500 12,300 12,100 11,790 11,4909,250
84 (28.9) SHC 14,230 14,030 13,830 13,520 13,220 10,980
88 (31.1) SHC 15,960 15,760 15,450 15,250 14,950 10,980
TC 19,880 19,350 18,760 18,220 17,460 11,160
72 (22.2) SHC 6,810 6,600 6,400 6,200 5,890 3,650
71 76 (24.4) SHC 8,540 8,330 8,130 7,930 7,620 5,380
(21.7) 80 (26.7) SHC 10,270 10,060 9,860 9,660 9,350 7,210
84 (28.9) SHC 12,000 11,790 11,590 11,390 11,0808,940
88 (31.1) SHC 13,720 13,520 13,320 13,110 12,810 10,670
TC 20,470 19,940 19,350 18,830 18,070 11,270
75 76 (24.4) SHC 6,300 6,200 5,990 5,790 5,490 3,350
(23.9) 80 (26.7) SHC 8,130 7,930 7,720 7,620 7,320 5,180
84 (28.9) SHC 9,860 9,660 9,450 9,350 9,050 6,910
88 (31.1) SHC 11,590 11,390 11,180 10,980 10,7808,640
TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)
1.
Rating conditions (#)
: Indoor Unit Entering Air Temp. 80 °F (26.7 °C) D.B. / 67 °F (19.4 °C) W.B.
: Outdoor Ambient Temp. 95 °F (35 °C) D.B.
2.
3. Above data represents the value when the operation frequency of a compressor is fixed.
Above data does not take Freeze Prevention Protection during cooling operation into account.
For this reason, the value may vary from the actual cooling characteristics.
NOTE