Sanyo C1852 Air Conditioner User Manual


 
– 29 –
SM830079
10. PROCESSES AND FUNCTIONS
(4) Outdoor Fan Speed Control (CL1852)
Low ambient fan speed control
This function protects the compressor from being damaged due to flowback of the
liquid refrigerant to the compressor when the outdoor temperature is very low.
When the air temp. thermistor (TH) on the outdoor units detects a change in tem-
perature, the controller on the electrical component box activates to control the
fanspeed automatically.
If the outdoor temperature falls below 57°F, the fan speed switches to MED.
If the outdoor temperature falls below 30°F, the fan speed switches to LOW.
57°F
30°F
Outdoor
temperature
Fan speed
*
1
Fan motor output
*
2
(Line voltage 115V or 230V)
HIGH
MEDIUM
LOW
31 (BLU–GRY) or (WHT–GRY)
51 (VLT–GRY)
71 (YEL–GRY)
1893_M_I
Fig. 11
*
1
Regardless of outdoor temperature, outdoor fan motor operates at first at HIGH
speed for 23 ± 5 seconds to give the motor an initial boost.
*
2
When the fan speed switches, the controller terminal’s location where line voltage
comes out () shifts accordingly.