Sanyo 85464359982001 Air Conditioner User Manual


 
24
X
3. HOW TO INSTALL THE INDOOR UNIT
4-Way Air Discharge Semi-Concealed Type (X Type)
3-1. Preparation for Suspending
This unit uses a drain pump. Use a carpenter’s level to check that the
unit is level.
3-2. Suspending the Indoor Unit
(1) Fix the suspension bolts securely in the ceiling using the method
shown in the diagrams (Figs. 3-1 and 3-2), by attaching them to
the ceiling support structure, or by any other method that ensures
that the unit will be securely and safely suspended.
(2) Follow Fig. 3-2 and Table 3-1 to make the holes in the ceiling.
Table 3-1
Unit: in. (mm)
(3) Determine the pitch of the suspension bolts using the supplied
full-scale installation diagram. The diagram and table (Fig. 3-3
and Table 3-2) show the relationship between the positions of the
suspension fitting, unit, and panel.
Table 3-2
Fig. 3-1
Fig. 3-2
e
-in-anchor
e
-in-plug
Concrete Insert
Suspension bolt (M10 or 3/8")
(field supply)
Type
ABCD
31-1/32
(788)
28-15/32
(723)
34-27/32
(885)
34-27/32
(885)
12, 18, 24, 36
Length
Type
ABCD
4-29/64
(113)
6-13/16
(173)
8-17/64
(210)
10-5/64
(256)
12, 18, 24
4-29/64
(113)
6-13/16
(173)
8-17/64
(210)
E
3-15/32
(88)
3-15/32
(88)
12-9/16
(319)
36
Length
C (ceiling opening dimension)
A (suspension bolt pitch)
B (suspension bolt pitch)
Drain outlet(other side)
(VP25)
Suspension lug
Refregerant tubing joint(liquid side) Refregerant tubing joint(gas side)
Power supply outlet
Inter-unit control wiring
D
E
A
B
C
1-3/8 (35)
Note: For DC Fan Tap Change Procedure
for 4-Way Cassette, see page 30.
Fig. 3-4
Full-scale installation diagram
(printed on top of container box)
Supplied bolt
Over 19/32 (15)
15/32 – 43/64
(12 – 17)
3-3. Placing the Unit Inside the Ceiling
(1) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts using the supplied
full-scale installation diagram. (Fig. 3-4)
Tubing and wiring must be laid inside the ceiling
when suspending the unit. If the ceiling is already
constructed, lay the tubing and wiring into position
for connection to the unit before placing the unit
inside the ceiling.
Unit: in. (mm)
Unit: in. (mm)
Unit: in. (mm)
Fig. 3-3
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 24