Samsung NH300WHXES Heat Pump User Manual


 
Appendix _43
ENGLISH
Appendix
TEMPERATURE TABLE
Available operation range
Mode Target temperature
Display Setting range
Current
display
Setting
method
Control
method
Set View Default Available
Cooling
Leaving water O O 16~25˚C
• Min : 5~18˚C
• Max : 18~25˚C
-50~94˚C Up/Down
Hydro or
Indoor unit
Room O O 18~30˚C
• Min : 18~22˚C
• Max : 24~30˚C
-50~94˚C Up/Down Indoor unit
Heating
Leaving water O O 25~55˚C
• Min : 15~37˚C
• Max : 37~55˚C
-50~94˚C Up/Down
Hydro or
Indoor unit
Room O O 16~30˚C
• Min : 16~22˚C
• Max : 24~30˚C
-50~94˚C Up/Down Indoor unit
Water
Law
Cooling
Outdoor X X 30~40˚C
• Min : 25~35˚C
• Max : 35~45˚C
-50~94˚C
Field
Setting
Mode
SET/VIEW
mode
Hydro unit
or
Thermostat
(Th-1 : Floor,
Th-2 : FCU)
Leaving water
(WL1-Floor)
X X 25~18˚C
• Min : 18~25˚C
• Max : 5~18˚C
-50~94˚C
Leaving water
(WL2-FCU)
X X 18~5˚C
• Min : 18~25˚C
• Max : 5~18˚C
-50~94˚C
Heating
Outdoor X X -10~15˚C
• Min : -20~5˚C
• Max : 10~20˚C
-50~94˚C
Leaving water
(WL1-Floor)
X X 40~25˚C
• Min : 40~55˚C
• Max : 17~37˚C
-50~94˚C
Leaving water
(WL2-FCU)
X X 50~35˚C
• Min : 40~55˚C
• Max : 17~37˚C
-50~94˚C
Temperature Shifting
O X -5~5˚C Default - Up/Down Hydro unit
DHW DHW tank O O 40~50˚C
• Min : 30~40˚C
• Max : 50~65˚C
-50~94˚C Up/Down Hydro unit
Outdoor temperature
X O - - -50~94˚C -
DIP SWITCH SETTING
S/W OFF (Default) ON
S/W #1 Heating and Cooling Heating only
S/W #2 Target temp : Water outlet Temp. Target temp : Indoor air Temp.
S/W #3 Air sensor in remote controller External air sensor
S/W #4 No Use No Use
S/W #5 No Use No Use
S/W #6 No Use No Use
S/W #7 No Use No Use
S/W #8 No Use No Use