P
REPARING THE INSTALLATION
Deciding on Where to Install the Air Conditioner(cont.)
Respect the clearances and maximum lengths indicated in the diagram below when installing the unit.
A
B
INDOOR UNIT
OUTDOOR UNIT
A
B
160 mm
(6 inch)
or more
25 mm (1 inch)
or more
◗ 26,000Btu/h
100 mm
(4 inch)
or more
100 mm
(4 inch)
minimum
600 mm
(24 inch)
minimum
600 mm (24 inch)
minimum
100 mm
(4 inch)
minimum
A-unit
12,500 Btu/h
B-unit
12,500 Btu/h
Circuit breaker
(20A)
Main power switch
B
(3 metres/9ft 10in maximum)
A
(15 metres/49ft 3in
maximum)
AM26A1C13 UM26A1C2 1,208-230~,60
Indoor unit Outdoor unit
Power supply
Ø, V, Hz
Piping length and the height.
A-unit
B-unit
Pipe size
Unit
Liquid
1/4
"
1/4
"
GAS
1/2
"
1/2
"
MAX.
piping length
A
15 m (49ft 3in)
15 m (49ft 3in)
MAX.
height
B
3 m (9ft 10in)
3 m (9ft 10in)
E-
28