Rinnai EX22C (RHFE-559FTA) Furnace User Manual


 
16 Rinnai Corporation EX17C / EX22C Manual
Gas Connection
The gas supply line shall be gas tight, sized and so
installed as to provide a supply of a gas sufficient to
meet the maximum demand of the heater without
loss of pressure.
A shut off valve and appliance connector valve
should be installed in the upstream of the gas line to
permit servicing.
Flexible pipe and any appliance connector valve
used for gas piping shall be types approved by
nationally recognized agencies.
Any compound used on the threaded joint of the gas
piping shall be a type which resists the action of
liquefied petroleum gas (propane / LPG).
After completion of gas pipe connections all joints
including the heater must be checked for gas
tightness by means of leak detector solution, soap
and water, or an equivalent nonflammable solution,
as applicable. (Since some leak test solutions,
including soap and water, may cause corrosion or
stress cracking, the piping shall be rinsed with water
after testing, unless it has been determined that the
leak test solution is non-corrosive.)
Check the gas supply pressure immediately
upstream at a location provided by the gas
company. Supplied gas pressure must be within the
limits shown in the Specifications section.
Refer to an approved pipe sizing chart if in doubt
about the size of the gas line.
Install the provided manual gas shut-off valve so
that it can be accessed for easy operation. Do not
conceal manual cut-off valve behind back spacer.
Clearances to Combustibles
When determining where to install the appliance
the clearances to combustibles shown in the
figure must be followed. Also refer to the Safety
Behaviors and Practices section.
Attach Back Covers (Sides Only)
Attach back covers as shown. Engage lugs
2 in
(50 mm)
2 in
(50 mm)
40
in
Manual gas
shut-off valve
The 40 inch (1 meter) clearance
from the front of the appliance does
not include flooring material or
carpeting that is less than 1.2 inches
(30 mm) in height.
NOTICE
0” (0 mm)
0” (0 mm)