Rheem Side Inlet Gas Water Heaters Water Heater User Manual


 
Venting System Inspection
It is recommended the water heater’s
internal flue be inspected annually to be
certain it is clean by removing the draft
hood and flue baffle.
When reinstalling the flue baffle make
certain it is hung securely by its hanger at
the top of the flue way.
Remove any scale that may have fallen on
the burner or floor shield and
reinstall the draft hood.
Make certain the draft hood is fastened to
the water heater top pan and roof jack vent
is properly positioned and securely
attached with sheet metal screws.
If after inspection of the vent system
you found sooting or deterioration
call the local gas utility to correct the
problem and clean or replace the flue
baffle and venting before resuming
operation of the water heater.
Test for spillage at the draft hood relief
opening after 5 minutes of burner
operation. Use a flame of a match or
candle or smoke.
Burner Inspection
Visually inspect the burners annually.
Through the site glass, inspect the pilot
burner flame with the main burner off and
inspect the main burner while firing.
If any unusual burner operation is noted,
the water heater should be shut off until
qualified service assistance can be
obtained.
For cleaning, remove the burner from the
water heater. A vacuum cleaner can be
used on the burner and floor shield inside
the water heater. The burner can also be
cleaned by scrubbing with mild detergent.
CAUTION: For your safety, cleaning of
the main burner should be performed only
by qualified service personnel.