Rheem PE Series Water Heater User Manual


 
8
Installing the water heater.
NOTICE: This guide recommends minimum branch circuit sizing and wire size based on National Electric Code.
Refer to wiring diagrams in this manual for field wiring connections.
Branch Circuit Sizing and Wire Size Guide
Total Water Recommended Over Current Protection Copper Wire Size AWG Based
Heater Wattage (fuse or circuit breaker amperage rating) on N.E.C. Table 310-16 (75°C)
208V 240V 277V 480V 208V 240V 277V 480V
3,000 20 20 15 15 12 12 14 14
4,000 25 25 20 15 10 10 12 14
4,500 30 25 25 15 10 10 10 14
5,000 30 30 25 15 10 10 10 14
5,500 35 30 25 15 8 10 10 14
6,000 40 35 30 20 8 8 10 12
8,000 50 45 40 25 8 8 8 10
9,000 50 45 25 8 8 10
10,000 50 30 8 10
11,000 50 30 8 10
12,000 35 8
Customer Service Troubleshooting Tips Care and Cleaning Operating Instructions Installation Instructions Safety Instructions
CAUTION: The presence
of water in the piping and
water heater does not
provide sufficient
conduction for a ground.
Non-metallic piping,
dielectric unions, flexible
connectors etc. can cause
the water heater to be
electrically isolated.
Electrical Connections
A separate branch circuit with copper
conductors, overcurrent protective device
and suitable disconnecting means must
be provided by a qualified electrician.
All wiring must conform to local codes
or latest edition of National Electrical
Code ANSI/NFPA 70.
The water heater is completely wired to
the junction box inside jacket at the top
front of the water heater. An opening for
1/2 or 3/4 electrical fitting is provided
for field wiring connections.
The voltage requirements and wattage
load for the water heater are specified
on the rating plate on the front of the
water heater.
The branch circuit wiring should
include either:
Metallic conduit or metallic
sheathed cable approved for use as
a grounding conductor and
installed with fittings approved for
the purpose.
Non-metallic sheathed cable,
metallic conduit or metallic
sheathed cable not approved for
use as a ground conductor shall
include a separate conductor for
grounding. It should be attached to
the ground terminals of the water
heater and the electrical
distribution box.