Rheem RSNA-B Series Air Conditioner User Manual


 
GROSS SYSTEMS PERFORMANCE DATA—RSNA-B048
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1760 [831] 1600 [755] 1360 [642] 1760 [831] 1600 [755] 1360 [642] 1760 [831] 1600 [755] 1360 [642]
DR
.20 .19 .17 .20 .19 .17 .20 .19 .17
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
60.8 [17.82]
36.3 [10.64]
2.9
59.7 [17.50]
34.7 [10.17]
2.9
58.1 [17.03]
32.3 [9.47]
2.9
56.4 [16.53]
41.5 [12.16]
2.9
55.4 [16.24]
39.7 [11.63]
2.9
53.9 [15.80]
36.9 [10.81]
2.9
53.1 [15.56]
48.2 [14.13]
2.9
52.2 [15.30]
46.0 [13.48]
2.8
50.8 [14.89]
42.8 [12.54]
2.8
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
59.9 [17.55]
35.2 [10.32]
3.1
58.8 [17.23]
33.7 [9.88]
3.1
57.2 [16.76]
31.3 [9.17]
3.0
55.5 [16.27]
40.4 [11.84]
3.1
54.5 [15.97]
38.6 [11.31]
3.1
53.0 [15.53]
35.9 [10.52]
3.0
52.3 [15.33]
47.1 [13.80]
3.0
51.3 [15.03]
45.0 [13.19]
3.0
49.9 [14.62]
41.8 [12.25]
3.0
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
58.8 [17.23]
34.3 [10.05]
3.3
57.7 [16.91]
32.8 [9.61]
3.2
56.1 [16.44]
30.5 [8.94]
3.2
54.4 [15.94]
39.5 [11.58]
3.3
53.4 [15.65]
37.7 [11.05]
3.2
51.9 [15.21]
35.1 [10.29]
3.2
51.1 [14.98]
46.1 [13.51]
3.2
50.2 [14.71]
44.1 [12.92]
3.2
48.8 [14.30]
41.0 [12.02]
3.1
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
57.4 [16.82]
33.5 [9.82]
3.4
56.4 [16.53]
32.0 [9.38]
3.4
54.8 [16.06]
29.8 [8.73]
3.4
53.0 [15.53]
38.7 [11.34]
3.4
52.0 [15.24]
37.0 [10.84]
3.4
50.6 [14.83]
34.4 [10.08]
3.4
49.7 [14.57]
45.3 [13.28]
3.4
48.8 [14.30]
43.4 [12.72]
3.3
47.5 [13.92]
40.3 [11.81]
3.3
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
55.9 [16.38]
33.1 [9.70]
3.6
54.9 [16.09]
31.6 [9.26]
3.6
53.4 [15.65]
29.4 [8.62]
3.5
51.5 [15.09]
38.3 [11.22]
3.6
50.6 [14.83]
36.6 [10.73]
3.6
49.2 [14.42]
34.0 [9.96]
3.5
48.2 [14.13]
45.0 [13.19]
3.5
47.4 [13.89]
42.9 [12.57]
3.5
46.1 [13.51]
39.9 [11.69]
3.5
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
54.3 [15.91]
33.0 [9.67]
3.8
53.3 [15.62]
31.5 [9.23]
3.7
51.9 [15.21]
29.3 [8.59]
3.7
49.9 [14.62]
38.2 [11.20]
3.8
49.0 [14.36]
36.5 [10.70]
3.7
47.7 [13.98]
34.0 [9.96]
3.7
46.7 [13.69]
45.0 [13.19]
3.7
45.8 [13.42]
42.9 [12.57]
3.7
44.6 [13.07]
39.9 [11.69]
3.6
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
52.8 [15.47]
33.4 [9.79]
3.9
51.8 [15.18]
31.9 [9.35]
3.9
50.4 [14.77]
29.7 [8.70]
3.9
48.4 [14.18]
38.6 [11.31]
3.9
47.5 [13.92]
36.9 [10.81]
3.9
46.2 [13.54]
34.3 [10.05]
3.9
45.1 [13.22]
45.1 [13.22]
3.9
44.3 [12.98]
43.2 [12.66]
3.9
43.1 [12.63]
40.2 [11.78]
3.8
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
51.3 [15.03]
34.4 [10.08]
4.1
50.4 [14.77]
32.9 [9.64]
4.1
49.0 [14.36]
30.6 [8.97]
4.0
46.9 [13.75]
39.6 [11.61]
4.1
46.1 [13.51]
37.8 [11.08]
4.1
44.8 [13.13]
35.2 [10.32]
4.0
43.6 [12.78]
43.6 [12.78]
4.1
42.9 [12.57]
42.9 [12.57]
4.0
41.7 [12.22]
41.1 [12.05]
4.0
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
50.0 [14.65]
36.0 [10.55]
4.3
49.1 [14.39]
34.4 [10.08]
4.2
47.8 [14.01]
32.0 [9.38]
4.2
45.6 [13.36]
41.2 [12.07]
4.3
44.8 [13.13]
39.4 [11.55]
4.3
43.6 [12.78]
36.6 [10.73]
4.2
42.3 [12.40]
42.3 [12.40]
4.2
41.6 [12.19]
41.6 [12.19]
4.2
40.4 [11.84]
40.4 [11.84]
4.1
GROSS SYSTEMS PERFORMANCE DATA—RSNA-B060
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 2040 [963] 1850 [873] 1570 [741] 2040 [963] 1850 [873] 1570 [741] 2040 [963] 1850 [873] 1570 [741]
DR
.21 .20 .18 .21 .20 .18 .21 .20 .18
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
69.9 [20.49]
41.5 [12.16]
3.9
68.7 [20.13]
39.7 [11.63]
3.8
66.8 [19.58]
36.9 [10.81]
3.8
66.3 [19.43]
48.8 [14.30]
3.8
65.1 [19.08]
46.7 [13.69]
3.7
63.3 [18.55]
43.4 [12.72]
3.7
63.8 [18.70]
53.0 [15.53]
3.7
62.6 [18.35]
50.6 [14.83]
3.7
60.9 [17.85]
47.1 [13.80]
3.7
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
69.6 [20.40]
40.4 [11.84]
4.1
68.4 [20.05]
38.6 [11.31]
4.0
66.5 [19.49]
35.9 [10.52]
4.0
65.9 [19.31]
47.8 [14.01]
4.0
64.8 [18.99]
45.6 [13.36]
4.0
63.0 [18.46]
42.4 [12.43]
3.9
63.4 [18.58]
51.9 [15.21]
3.9
62.3 [18.26]
49.6 [14.54]
3.9
60.6 [17.76]
46.1 [13.51]
3.9
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
68.5 [20.08]
39.4 [11.55]
4.3
67.3 [19.72]
37.6 [11.02]
4.3
65.4 [19.17]
35.0 [10.26]
4.2
64.8 [18.99]
46.7 [13.69]
4.2
63.7 [18.67]
44.6 [13.07]
4.2
61.9 [18.14]
41.5 [12.16]
4.1
62.3 [18.26]
50.9 [14.92]
4.2
61.2 [17.94]
48.6 [14.24]
4.1
59.5 [17.44]
45.2 [13.25]
4.1
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
66.8 [19.58]
38.3 [11.22]
4.5
65.6 [19.23]
36.6 [10.73]
4.5
63.9 [18.73]
34.0 [9.96]
4.4
63.2 [18.52]
45.7 [13.39]
4.4
62.0 [18.17]
43.6 [12.78]
4.4
60.4 [17.70]
40.6 [11.90]
4.3
60.7 [17.79]
49.8 [14.59]
4.4
59.6 [17.47]
47.6 [13.95]
4.3
58.0 [17.00]
44.3 [12.98]
4.3
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
64.8 [18.99]
37.3 [10.93]
4.7
63.7 [18.67]
35.6 [10.43]
4.7
61.9 [18.14]
33.1 [9.70]
4.6
61.2 [17.94]
44.6 [13.07]
4.6
60.1 [17.61]
42.6 [12.48]
4.6
58.4 [17.12]
39.7 [11.63]
4.5
58.7 [17.20]
48.8 [14.30]
4.6
57.6 [16.88]
46.6 [13.66]
4.5
56.0 [16.41]
43.4 [12.72]
4.5
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
62.7 [18.38]
36.3 [10.64]
4.9
61.6 [18.05]
34.7 [10.17]
4.9
59.9 [17.55]
32.3 [9.47]
4.8
59.0 [17.29]
43.6 [12.78]
4.8
58.0 [17.00]
41.7 [12.22]
4.8
56.4 [16.53]
38.8 [11.37]
4.7
56.5 [16.56]
47.8 [14.01]
4.8
55.5 [16.27]
45.7 [13.39]
4.8
54.0 [15.83]
42.5 [12.46]
4.7
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
60.6 [17.76]
35.3 [10.35]
5.1
59.6 [17.47]
33.8 [9.91]
5.1
57.9 [16.97]
31.4 [9.20]
5.0
57.0 [16.71]
42.7 [12.51]
5.1
55.9 [16.38]
40.8 [11.96]
5.0
54.4 [15.94]
37.9 [11.11]
4.9
54.5 [15.97]
46.9 [13.75]
5.0
53.5 [15.68]
44.8 [13.13]
5.0
52.0 [15.24]
41.6 [12.19]
4.9
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
58.8 [17.23]
34.4 [10.08]
5.3
57.8 [16.94]
32.9 [9.64]
5.3
56.2 [16.47]
30.6 [8.97]
5.2
55.2 [16.18]
41.8 [12.25]
5.3
54.2 [15.88]
39.9 [11.69]
5.2
52.7 [15.44]
37.1 [10.87]
5.2
52.7 [15.44]
45.9 [13.45]
5.2
51.7 [15.15]
43.9 [12.87]
5.2
50.3 [14.74]
40.8 [11.96]
5.1
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
57.5 [16.85]
33.5 [9.82]
5.6
56.5 [16.56]
32.0 [9.38]
5.5
55.0 [16.12]
29.8 [8.73]
5.4
53.9 [15.80]
40.9 [11.99]
5.5
52.9 [15.50]
39.1 [11.46]
5.4
51.4 [15.06]
36.3 [10.64]
5.4
51.3 [15.03]
45.0 [13.19]
5.4
50.4 [14.77]
43.0 [12.60]
5.4
49.0 [14.36]
40.0 [11.72]
5.3
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power—KW input
NOTES: When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
[ ] Designates Metric Conversions
13
SYSTEMS PERFORMANCE—RSNA-B SERIES