Rheem RSNA-B Series Air Conditioner User Manual


 
12
SYSTEMS PERFORMANCE—RSNA-B SERIES
GROSS SYSTEMS PERFORMANCE DATA—RSNA-B036
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1320 [623] 1200 [566] 1020 [481] 1320 [623] 1200 [566] 1020 [481] 1320 [623] 1200 [566] 1020 [481]
DR
.21 .20 .17 .21 .20 .17 .21 .20 .17
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
44.4 [13.01]
25.5 [7.47]
2.2
43.6 [12.78]
24.4 [7.15]
2.1
42.4 [12.43]
22.7 [6.65]
2.1
41.3 [12.10]
30.4 [8.91]
2.1
40.6 [11.90]
29.1 [8.53]
2.1
39.5 [11.58]
27.0 [7.91]
2.1
39.6 [11.61]
31.4 [9.20]
2.1
38.9 [11.40]
30.0 [8.79]
2.1
37.8 [11.08]
27.9 [8.18]
2.1
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
43.6 [12.78]
25.0 [7.33]
2.3
42.8 [12.54]
23.9 [7.00]
2.3
41.7 [12.22]
22.2 [6.51]
2.2
40.5 [11.87]
29.9 [8.76]
2.3
39.8 [11.66]
28.6 [8.38]
2.3
38.7 [11.34]
26.6 [7.80]
2.2
38.7 [11.34]
30.8 [9.03]
2.3
38.0 [11.14]
29.5 [8.65]
2.3
37.0 [10.84]
27.4 [8.03]
2.2
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
42.8 [12.54]
24.5 [7.18]
2.4
42.1 [12.34]
23.4 [6.86]
2.4
40.9 [11.99]
21.8 [6.39]
2.4
39.7 [11.63]
29.4 [8.62]
2.4
39.0 [11.43]
28.1 [8.24]
2.4
38.0 [11.14]
26.1 [7.65]
2.4
38.0 [11.14]
30.3 [8.88]
2.4
37.3 [10.93]
29.0 [8.50]
2.4
36.3 [10.64]
27.0 [7.91]
2.4
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
42.0 [12.31]
24.0 [7.03]
2.6
41.3 [12.10]
22.9 [6.71]
2.5
40.2 [11.78]
21.3 [6.24]
2.5
38.9 [11.40]
28.9 [8.47]
2.6
38.3 [11.22]
27.6 [8.09]
2.5
37.2 [10.90]
25.7 [7.53]
2.5
37.2 [10.90]
29.9 [8.76]
2.5
36.5 [10.70]
28.5 [8.35]
2.5
35.5 [10.40]
26.5 [7.77]
2.5
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
41.1 [12.05]
23.5 [6.89]
2.7
40.4 [11.84]
22.4 [6.56]
2.7
39.3 [11.52]
20.9 [6.13]
2.6
38.0 [11.14]
28.4 [8.32]
2.7
37.4 [10.96]
27.1 [7.94]
2.7
36.3 [10.64]
25.2 [7.39]
2.6
36.3 [10.64]
29.3 [8.59]
2.7
35.6 [10.43]
28.0 [8.21]
2.7
34.7 [10.17]
26.0 [7.62]
2.6
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
40.0 [11.72]
22.8 [6.68]
2.8
39.3 [11.52]
21.8 [6.39]
2.8
38.2 [11.20]
20.3 [5.95]
2.8
36.9 [10.81]
27.7 [8.12]
2.8
36.3 [10.64]
26.5 [7.77]
2.8
35.3 [10.35]
24.6 [7.21]
2.8
35.2 [10.32]
28.7 [8.41]
2.8
34.5 [10.11]
27.4 [8.03]
2.8
33.6 [9.85]
25.5 [7.47]
2.8
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
38.6 [11.31]
22.1 [6.48]
3.0
37.9 [11.11]
21.1 [6.18]
3.0
36.9 [10.81]
19.6 [5.74]
2.9
35.5 [10.40]
26.9 [7.88]
3.0
34.9 [10.23]
25.7 [7.53]
2.9
33.9 [9.94]
23.9 [7.00]
2.9
33.8 [9.91]
27.9 [8.18]
3.0
33.2 [9.73]
26.6 [7.80]
2.9
32.3 [9.47]
24.8 [7.27]
2.9
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
36.9 [10.81]
21.1 [6.18]
3.1
36.2 [10.61]
20.1 [5.89]
3.1
35.2 [10.32]
18.7 [5.48]
3.1
33.8 [9.91]
26.0 [7.62]
3.1
33.1 [9.70]
24.8 [7.27]
3.1
32.2 [9.44]
23.1 [6.77]
3.0
32.0 [9.38]
26.9 [7.88]
3.1
31.4 [9.20]
25.7 [7.53]
3.1
30.6 [8.97]
23.9 [7.00]
3.0
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
34.6 [10.14]
19.9 [5.83]
3.3
34.0 [9.96]
19.0 [5.57]
3.2
33.1 [9.70]
17.7 [5.19]
3.2
31.5 [9.23]
24.8 [7.27]
3.2
30.9 [9.06]
23.7 [6.95]
3.2
30.1 [8.82]
22.0 [6.45]
3.2
29.7 [8.70]
25.7 [7.53]
3.2
29.2 [8.56]
24.6 [7.21]
3.2
28.4 [8.32]
22.9 [6.71]
3.2
GROSS SYSTEMS PERFORMANCE DATA—RSNA-B042
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1490 [703] 1350 [637] 1150 [543] 1490 [703] 1350 [637] 1150 [543] 1490 [703] 1350 [637] 1150 [543]
DR
.24 .23 .21 .24 .23 .21 .24 .23 .21
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
51.1 [14.98]
28.1 [8.24]
2.6
50.2 [14.71]
26.9 [7.88]
2.6
48.8 [14.30]
25.0 [7.33]
2.5
47.7 [13.98]
33.4 [9.79]
2.5
46.9 [13.75]
31.9 [9.35]
2.5
45.6 [13.36]
29.7 [8.70]
2.5
45.2 [13.25]
37.9 [11.11]
2.5
44.3 [12.98]
36.2 [10.61]
2.5
43.1 [12.63]
33.6 [9.85]
2.5
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
50.1 [14.68]
27.9 [8.18]
2.7
49.2 [14.42]
26.7 [7.83]
2.7
47.8 [14.01]
24.8 [7.27]
2.7
46.7 [13.69]
33.2 [9.73]
2.7
45.9 [13.45]
31.7 [9.29]
2.7
44.6 [13.07]
29.5 [8.65]
2.6
44.1 [12.92]
37.6 [11.02]
2.7
43.3 [12.69]
36.0 [10.55]
2.7
42.2 [12.37]
33.5 [9.82]
2.6
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
49.0 [14.36]
27.5 [8.06]
2.9
48.1 [14.10]
26.3 [7.71]
2.8
46.8 [13.72]
24.5 [7.18]
2.8
45.6 [13.36]
32.8 [9.61]
2.8
44.8 [13.13]
31.3 [9.17]
2.8
43.6 [12.78]
29.1 [8.53]
2.8
43.1 [12.63]
37.2 [10.90]
2.8
42.3 [12.40]
35.6 [10.43]
2.8
41.1 [12.05]
33.1 [9.70]
2.8
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
47.9 [14.04]
27.0 [7.91]
3.0
47.0 [13.77]
25.8 [7.56]
3.0
45.8 [13.42]
24.0 [7.03]
2.9
44.5 [13.04]
32.2 [9.44]
3.0
43.7 [12.81]
30.8 [9.03]
3.0
42.5 [12.46]
28.6 [8.38]
2.9
42.0 [12.31]
36.7 [10.76]
3.0
41.2 [12.07]
35.0 [10.26]
2.9
40.1 [11.75]
32.6 [9.55]
2.9
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
46.8 [13.72]
26.3 [7.71]
3.2
45.9 [13.45]
25.1 [7.36]
3.1
44.7 [13.10]
23.4 [6.86]
3.1
43.4 [12.72]
31.5 [9.23]
3.1
42.6 [12.48]
30.1 [8.82]
3.1
41.4 [12.13]
28.0 [8.21]
3.1
40.8 [11.96]
36.0 [10.55]
3.1
40.1 [11.75]
34.4 [10.08]
3.1
39.0 [11.43]
32.0 [9.38]
3.0
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
45.6 [13.36]
25.6 [7.50]
3.3
44.8 [13.13]
24.4 [7.15]
3.3
43.6 [12.78]
22.7 [6.65]
3.2
42.2 [12.37]
30.8 [9.03]
3.3
41.5 [12.16]
29.4 [8.62]
3.2
40.4 [11.84]
27.4 [8.03]
3.2
39.7 [11.63]
35.3 [10.35]
3.3
39.0 [11.43]
33.7 [9.88]
3.2
37.9 [11.11]
31.3 [9.17]
3.2
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
44.5 [13.04]
24.8 [7.27]
3.4
43.7 [12.81]
23.7 [6.95]
3.4
42.5 [12.46]
22.1 [6.48]
3.4
41.1 [12.05]
30.1 [8.82]
3.4
40.4 [11.84]
28.7 [8.41]
3.4
39.3 [11.52]
26.7 [7.83]
3.3
38.6 [11.31]
34.5 [10.11]
3.4
37.9 [11.11]
33.0 [9.67]
3.4
36.8 [10.79]
30.7 [9.00]
3.3
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
43.4 [12.72]
24.2 [7.09]
3.6
42.6 [12.48]
23.1 [6.77]
3.6
41.5 [12.16]
21.5 [6.30]
3.5
40.0 [11.72]
29.4 [8.62]
3.6
39.3 [11.52]
28.1 [8.24]
3.5
38.2 [11.20]
26.1 [7.65]
3.5
37.5 [10.99]
33.9 [9.94]
3.5
36.8 [10.79]
32.4 [9.50]
3.5
35.8 [10.49]
30.1 [8.82]
3.5
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
42.3 [12.40]
23.6 [6.92]
3.7
41.6 [12.19]
22.5 [6.59]
3.7
40.4 [11.84]
21.0 [6.15]
3.7
39.0 [11.43]
28.8 [8.44]
3.7
38.3 [11.22]
27.5 [8.06]
3.7
37.2 [10.90]
25.6 [7.50]
3.6
36.4 [10.67]
33.3 [9.76]
3.7
35.7 [10.46]
31.8 [9.32]
3.7
34.8 [10.20]
29.6 [8.67]
3.6
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power—KW input
NOTES: When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
[ ] Designates Metric Conversions