CONNECTIONS – ELECTRICAL
31
POWER FLUE EXTERNAL CONTROLS – 24 HOUR OPERATION
Notes:
1. Power source for the water heater, fan and control circuit must be from the same
circuit.
2. R1 monitors return signal.
3. R2 monitors alarm signal.
4. T1 to be set for 20-30 seconds.
5. Use SPO with round earth terminal. Water heater supply cord must be changed to
suit.
6. Meets requirements of Clause H.2.2.6 of AS5601 – 2004, providing lockout in the
event of flue product flow failure.