Sediment and lime scale removal may be accomplished through the
cleanout opening furnished on the heater, see Figure 25. The heater
must be drained, see DRAINING, before removing cleanout cover
on tank.
FIGURE 16.
To dissolve and remove the more stubborn mineral deposits, UN•LIME®
Professional Delimer should be used.
The cleanout opening is shown in Figure 16. To clean heater through cleanout
opening, proceed as follow:
1. Turn off water inlet valve, the heater electrical disconnect switch and open
drain valve.
2. Remove outer cover plate from lower side of heater jacket.
3. Remove cover from cleanout opening.
4. Remove lime, scale or sediment using care not to damage the
glass-lining.
5. Inspect cleanout plate gasket: If new gasket is required, replace with
part number indicated in the Replacement Parts List.
6. Install cleanout plate. Be sure to draw plate up tight by tightening screws
securely.
7. Close drain valve, open water inlet line and turn on the power burner
electrical disconnect switch.
8. Check for water leakage.
9. Replace outer jacket cover plate.
POWERED ANODE SYSTEM
The RUF heaters are factory equipped with a powered anode system.
The anodes are of a permanent design and do not need replacing unless
damaged.
FLUSHING
1. Turn off the heater electrical disconnect switch.
2. Open the drain valve and allow water to ow until it runs clean.
3. Close the drain valve when nished ushing.
4. Turn on the heater electrical disconnect switch.
DRAINING
The heater must be drained if it is to be shut down and exposed to freezing
temperatures. Maintenance and service procedures may also require draining
the heater.
1. Turn off the heater electrical disconnect switch.
2. Close the cold water inlet valve to heater.
3. Open a nearby hot water faucet to vent the system.
4. Open the heater drain valve.
5. If the heater is being drained for an extended shutdown, it is suggested
the drain valve be left open during this period.
• Follow FILLING instructions when restoring hot water service.
SEDIMENT REMOVAL
Waterborne impurities consist of the particles of soil and sand which settle
out and form a layer of sediment on the bottom of the tank.
For convenience, sediment removal and lime scale removal should be
performed at the same time.
LIME SCALE REMOVAL
The amount of calcium carbonate (lime) released from water is in direct
proportion to water temperature and usage. The higher the water temperature
or water usage, the more lime deposits are dropped out of the water. This is
the lime scale which forms in pipes, heaters and on cooking utensils.
Lime accumulation not only reduces the life of the equipment but also reduces
efciency of the heater and increases fuel consumption.
The usage of water softening equipment greatly reduces the hardness of the
water. However, this equipment does not always remove all of the hardness
(lime). For this reason it is recommended that a regular schedule for deliming
be maintained.
The depth of lime buildup should be measured periodically. Heaters will have
about 3" (7.6cm) of lime buildup when the level of lime has reached the bottom
of the cleanout opening or about 1" (2.5cm) of lime buildup if it has reached
the drain valve opening. A schedule for deliming should be set up, based on
the amount of time it would take for a 1" (2.5cm) buildup of lime.
Example 1:
Initial inspection shows 1/2" (1.3cm) of lime accumulation. Therefore, the
heater can be delimed once a year.
Example 2 :
Initial inspection shows 2" (5cm) of lime accumulation. Therefore, the
heater should be delimed every 3 months.