Regency U39-NG1 Stove User Manual


 
Regency
®
U39 ULTIMATE Direct Vent Freestanding Gas Stove
9
EXTERIOR VENT TERMINAL LOCATIONS
A= Clearance above grade, veranda, porch, deck, or balcony *(min.
12"/30cm)
B= Clearance to window or door that may be opened *(12"/30cm)
C= Clearance to permanently closed window *(min. 12"/30cm)
D= Vertical clearance to ventilated soffi t located above the terminal within a
horizontal distance of (24"/60cm) from the centerline of the terminal (min.
18"/46cm) check with local code.
E= Clearance to unventilated soffi t (min. 12"/30cm)
F= Clearance to outside corner: with AstroCap Termination Cap (min. 6"/15cm),
with Dura-Vent termination cap (min. 12"/30cm)
G= Clearance to inside corner: with AstroCap Termination Cap (min. 6"/15cm),
with Dura-Vent termination cap (min. 12"/30cm)
H= Not to be installed above a meter/regulator assembly within (3'/90cm)
horizontally from the centerline of the regulator.
J= Clearance to service regulator vent outlet *(min. 36"/90cm)
K= Clearance to non-mechanical air supply inlet to building or the combustion
air inlet to any other appliance *(12"/30cm)
L= Clearance to a mechanical air supply inlet *(min. 72"/1.8m)
M= **Clearance above paved sidewalk or a paved driveway located on public
property *(min. 84"/2.1m)
N= Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)***
Note: * As specifi ed in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances.
**A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
INSTALLATION