Horizontal Terminations for All
Venting Systems
The shaded areas in the diagram below show all allowable combinations
of vertical runs with horizontal terminations. Maximum one 90° elbow
(two 45º
elbows equal one 90° elbow).
Propane and Natural Gas:
Residential, Manufactured and Mobile Homes
Installations
The venting arrangements diagrammed below, have a min. of 75%
(fl ue loss) effi ciency with Fan Off, as required for manufactured homes.
(Actual effi ciency may be as high as 85%)
May be installed in Manufactured (Mobile) Homes after fi rst sale.
U39 Gas Stove
Horizontal Venting with Two (2) 90°
Elbows
Two 45° elbows = One 90° elbow
Option V H + H1 Maximum total pipe length, of all
sections, must not exceed 30 feet.
Total horizontal sections must not
exceed 4 feet.
Minimum of 1 foot between 90°
elbows is required.
A) 3’ Min. 2’ Max.
B) 5’ Min. 3’ Max.
C) 8’ Min. 4’ Max.
Vent Restrictor in position “A” (Center), refer to page 124.