Vertical Terminations using Rigid
Pipe Systems
The shaded area in the diagram below shows all allowable combinations
of straight vertical and offset to vertical runs with vertical terminations.
Maximum two 45º elbows.
If the vent is ENCLOSED in a chase (min. size 9" x 9") maintain a 1-1/4"
clearance to combustibles.
May be installed in Manufactured (Mobile) Homes after fi rst sale.
Vertical Venting with Two (2) 90° Elbows
Two 45° elbows = One 90° elbow
Option V H V+ V1 Maximum total pipe length, of
all sections, must not exceed
30 feet.
Total horizontal sections must
not exceed 4 feet.
Minimum of 1 foot between
90° elbows is required.
A) 1’ Min. 1’ Max. 2’ Min.
B) 1’ Min. 2’ Max. 3’ Min.
C) 2’ Min. 3’ Max. 4’ Min.
D) 2’ Min. 4’ Max. 4’ Min.
Vent Restrictor in position “A” (Center), refer to page 124.
159June 2007 Regency Product Specifi cations Book