Regency P48-NG2 Indoor Fireplace User Manual


 
Pipe Length
Vertical
Terminal
Storm Collar
Flashing
Ceiling Firestop
24" Length
Adj.Pipe Length
11" - 14-5/8”
90 Elbow
o
Horizontal
Termination Cap
# 946-623/P
WallThimble
Vinyl Siding
Standoff
Rigid PipeAdapter
# 770-994
45 Elbow
o
Adj.Pipe Length
11" - 14-5/8”
Horizontal
Termination Cap
# 946-623/P
WallThimble
Vinyl Siding
Standoff
Rigid Pipe Venting
Horizontal or Vertical Terminations
Venting Arrangements - Vertical
Terminations
Rigid Pipe System
(Propane & Natural Gas)
The P48 is approved for a maximum 40 ft. straight vertical, with Rigid
Pipe vent systems for Propane and Natural Gas.
The lightly shaded area,
6
8
2
0
4
10
0
2
4
6
40
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
12
, in the diagram shows allowable venting
confi gurations with a maximum two 45° elbows allowed.
The darker shaded area,
6
8
2
0
4
10
0
2
4
6
40
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
12
, in the diagram shows allowable venting
confi gurations using 45° and one 90° elbow.
Vent must be supported at offsets.
Horizontal sections must be supported every 3 feet.
Firestops are required at each floor level and whenever
passing through a wall.
Maintain clearances to combustible materials.
Minimum of 1’ pipe section between elbows.
Note: Must use optional fl ue adapter when using Rigid Pipe (Part
# 770-994).
Maximum: 40 ft. (12.2m)
Minimum 10’6” (3.2m)
Minimum 8’6” (2.6m)
Max. 10’ (3m)(centerline to centerline)
Minimum 12” (305mm)
Maximum: 27 ft. (8.2m)
0
2
4
6
40
8
10
12
14
16
18
20
22
24
26
28
30
Vertical Height (Feet)
32
34
36
38
6
8
2
0
4
10 12
12 16
18
14
20 26
28
22 24
30
P48 Gas Fireplace
If required by the external termination location the listed
alternate termination caps may be used. (Refer to Page 11)
Alternate Horizontal
Termination Caps
Alternate Snorkel
Termination Cap
Part #1282 (14”)
Part #1281 (36”)
64 June 2007 Regency Product Specifi cations Book
Gas Fireplaces
Gas Fireplaces