Regency P42-LP4 Indoor Fireplace User Manual


 
Regency
®
P42-4 Zero Clearance Direct Vent Gas Fireplace
14
Rigid Pipe Adaptor
(Part# 510-994)
Pipe Length
Vertical
Terminal
Storm Collar
Part # 953
Flashing
943 or 943S
Ceiling Firestop
(Part # 963)
24" Pipe
Length
Adj.Pipe Length
11" - 14-5/8"
90 Elbow
o
Horizontal
Terminatio
n
Cap
Wall Thimble
Part # 942
Vinyl Siding
Standoff (Optional)
Part #950
RIGID PIPE VENTING
Horizontal or Vertical Terminations
The Rigid Pipe Venting System offers a complete line of component parts for installation of both horizontal and vertical installations. Many items are
offered in decorative black, as well as galvanized fi nish. We recommend using the galvanized fi nish for installation with the P42.
The minimum components required for a basic
horizontal termination are:
1 Horizontal Termination Cap
1 90
o
Elbow
1 Flue Adaptor
1 Wall Thimble
1 Length of pipe to suit wall thickness
(see chart)
Alternate
Horizontal
Termination Caps
INSTALLATION
Flat Wall Installation
Wall Thickness Vent Length
(inches) Required (inches)
4" - 5-1/2" 6"
7" - 8-1/2" 9"
10" - 11-1/2" 12"
9" - 14-1/2" 11" - 14-5/8" Adj. Pipe
15" - 23-1/2" 17" - 24" Adj. Pipe
Corner Installation
Wall Thickness Vent Length
(inches) Required (inches)
3-1/4" - 6-3/4"11" - 14-5/8" Adj. Pipe
7-3/4" - 16-1/4" 17" - 24" Adj. Pipe
7-1/4" - 8-3/4" 6" + 12"
9" + 9"
4-1/4" - 5-3/4" 6" + 9"
Wall thickness is measured from the back
standoffs to the inside mounting surface of
termination cap. For siding other than vinyl
furring strips may be used, instead of the vinyl
siding standoff, to create a level surface to
mount the vent terminal. The Terminal must
not be recessed into siding. Measure the wall
thickness including furring strips.
If a Vinyl Siding Standoff is required (it must
be used with vinyl siding), measure to outside
surface of wall without siding and add 2
inches.
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
The FPI AstroCap
TM
and FPI Riser Vent terminal are certifi ed for installations using FPI venting systems as well as Simpson Dura-Vent
®
Direct Vent GS,
American Metal Products Ameri Vent Direct Vent, Security Secure Vent
®
, Selkirk Direct-Temp. AstroCap
TM
is a proprietary trademark of FPI Fireplace
Products International Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
This product has been evaluated by Intertek for
using a Rigid Pipe Adaptor in conjunction with
Duravent Direct-Vent GS, Selkirk Direct-Temp,
Ameri Vent Direct venting and Security Secure
Vent systems. Use of these systems with the
Rigid Pipe adaptor is deemed acceptable
and does not affect the Intertek WHI listing of
components.
WARNING:
Do not combine venting components from
different venting systems.
However use of the the AstroCap
TM
and FPI
Riser is acceptable with all systems.