Regency F1100S Stove User Manual


 
Regency Freestanding Woodstove
8
INSTALLATION
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
Please read the section below carefully as clearances depend on whether the airmate or the rear heat deflector is installed on the stove.
Measurements "From Unit" are from the top plate of the stove to a side wall or to a corner, and from the rear heat shield to a back wall.
Mobile Home Close Clearance (To be installed with required pipe components)
"C" Vent single wall pipe is not approved for Mobile Home installations. (Refer to Mobile Home Instructions.)
Unit From Unit From Corner From Flue Center-line
ABCDEF
Small F1100S with Airmate 11" 6" 6" 23" 12.5" 18"
with Rear Deflector 13" 5" 9" 25" 11.5" 21"
Large F3100L with Airmate 18" 9.5" 10" 32" 16" 23.5"
with Rear Deflector 20" 12" 10" 34" 18.5" 23.5"
Large S3100L Step Stove 18" 9.5" 10" 32" 16" 23.5"
Residential Installation “C” Vent (Single Wall)
Unit From Unit From Corner From Flue Center-line
ABCDEF
Small F1100S with Airmate 13" 11" 8" 25" 17.5" 20"
with Rear Deflector 15" 10.5" 11" 27" 17" 23"
Large F3100L with Airmate 18" 12" 8.5" 32" 18.5" 22"
with Rear Deflector 20" 14" 10.5" 34" 20.5" 24"
Large S3100L Step Stove 18" 12" 8.5" 32" 18.5" 22"
Residential Close Clearance (To be installed with required pipe components)
When the stove is installed as a close clearance residential unit, a listed double wall connector is required from the stove
collar to the ceiling level.
Unit From Unit From Corner From Flue Center-line
ABCDEF
Small F1100S with Airmate 9" 5" 3" 21" 11.5" 15"
with Rear Deflector 13.5" 5" 5" 25.5" 11.5" 17"
Large F3100L with Airmate 16" 9.5" 8.5" 30" 16" 22"
with Rear Deflector 20" 12" 8.5" 34" 18.5" 22"
Large S3100L Step Stove 16" 9.5" 8.5" 30" 16" 22"