Regency CS1200 Stove User Manual


 
Regency CS1200 Freestanding Wood Stove
7
INSTALLATION
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS
MEASUREMENTS "FROM UNIT" ARE FROM THE SIDE SHIELDS OF THE STOVE TO A SIDE WALL OR TO A CORNER, AND
FROM THE REAR HEAT SHIELD TO A BACK WALL
NOTE: Be aware that local Codes and Regulations may override some clearances listed in this manual.
Check with your local inspector.
Residential Installation “C” Vent (Single Wall)
Unit From Unit From Corner From Flue Center-line
CS1200
ABCDEF
13" 11" 8" 26-3/8" 18-1/2" 20-3/4"
Residential Close Clearance (To be installed with required pipe components)
When the stove is installed as a close clearance residential unit, a listed double wall connector is required from
the stove collar to the ceiling level.
From Unit From Corner From Flue Center-line
CS1200
ABCDEF
11" 7" 7" 24-1/2" 14.5" 19-3/4"
Mobile Home Close Clearance (To be installed with required pipe components)
"C" Vent single wall pipe is not approved for Mobile Home installations. (Refer to Mobile Home Instructions.)
From Unit From Corner From Flue Center-line
CS1200
ABCDEF
11" 7" 7" 24-1/2" 14.5" 19-3/4"
A
F
F
C
C
BE
D