Regency Bellavista B36X Gas Fireplace
Rear Vent with Horizontal Termination
(see Diagram 1)
• Can only use 5” x 8” venting
• Maximum 20 ft. horizontal vent run
• Use either 5” x 8” AstroCap
TM
Flex Vent or approved Rigid Vent System
with Rigid Pipe Adaptor (770-994)
• Horizontal vent must be supported every 3 feet
B36X Gas Fireplace
Diagram 3
Diagram 4
Top Vent with Horizontal Termination
• Top Vent Reducer [5” x 8” to 4’” x 6-5/8”]
- For use with Top Vent, Rigid Venting applications only.
• Must use Rigid Pipe Adaptor (770-994) and reducer (946-606) for all
applications
• Horizontal vent must be supported every 3 feet
• Maximum 20 ft. horizontal vent run
Top Vent - No Vertical Rise (see Diagram 3)
• When venting with a 90
o
elbow directly off the unit, must use 5” x
8” AstroCap
TM
Flex Vent or approved Rigid Vent System
Top Vent - With Vertical Rise (see Diagram 4)
• All vent confi gurations can use either 5” x 8” or 4” x 6-5/8” (reducer
required 946-606) approved Rigid Vent System.
Diagram 2
Diagram 1
Top Vent with Vertical Termination
(see Diagram 2)
• All vent confi gurations can use either 5” x 8” or 4” x 6-5/8” (reducer
required 946-606) approved Rigid Vent System.
• Must use Rigid Pipe Adaptor (770-994) for all applications.
• Maximum 40 ft. vent run