Raypak Y-200 Boiler User Manual


 
34
Press MODE button to get into program mode.
Go to screen number 25 and select the number of slaves you wish to use, 01 thru 04.
SL AVES CONNECTED 25
#XX
Go to screen number 24 and select the number of sensors, relays and auxiliaries.
42RETSAM
SN S : X RE L AY : X AUX : X
02PU-TESKROWTEN
MASTER PBXXXXXXXXXX
Screen number
Screen number
Screen number
Go to screen number 20 and set up your Network master and slave operations.
(Setup slave operations prior to Network Set-up on Master Controller.)
PI D INTERVAL XX 34
KP XX K I XX KD XX
Screen number
PID
Proportional - Integral - Derivative Control
I
nterval - time in seconds that the PID updates
KP - Proportional control (01 - 30) - Band in degrees above and below setpoint
K
I - Integral control (01 - 99) - Adjustable in % 0.0 - 1.0
KD - Derivative control (01 - 99) - Adjustable in % 0.0 - 10.0
PID Interval:
Default Values: Interval=05; KP=06; KI=05; KD=01
NOTE: DO NOT change the default values unless
directed to do so in consultation with factory
technical support. Changing of these parameters
may create adverse operating conditions.
NOTE: Refer to screen number 34 (PID)
Master Unit with Slaves
Refer to page 36 for the Master/Slave diagram.