Raypak 5300 Heat Pump User Manual


 
10
Plumbing Diagrams
For systems with pumps of 2 HP or greater (over 80 gpm), an external
bypass is required. Adjust the bypass valve to divert a minimum of 40
gpm through the heat pump. Connections are 2-inch unions. Plumb the
heat pump after the filter and before any chlorinators.
Water In
(from pool
or spa)
Water Out
(to pool
or spa)
Filter
For systems with pumps of less than 2 HP (under 80 gpm), no external
bypass is required. Connections are 2-inch unions. Plumb the heat
pump after the filter and before any chlorinators.
Water In
(from pool
or spa)
Water Out
(to pool
or spa)
Filter