17
For Standing Pilot Model with
Robertshaw Gas Valve, On/Off
Operation
1. STOP! Read the safety information.
2. Set the tankstat on the lowest setting.
3. Turn OFF all electric power to the heater.
4. Remove heater door panel.
5. Push in gas control knob slightly and turn clock-
wise to "OFF".
6. Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If your smell
gas, STOP! Follow "B" in the safety information
above on this label. If you don't smell gas, go to
the next step.
7. Locate pilot behind gas valve mounted on the
base panel of the burner drawer.
8. Turn knob on gas control counter-clockwise
to "Pilot".
GAS CONTROL
KNOB SHOWN
IN "OFF" POSITION
GAS INLE
T
Fig. 9: Robertshaw Gas Valve
NOTE: Knob cannot be turned from "PILOT" to
"OFF" unless knob is pushed in slightly. Do not force.
HONEYWELL PILOT ROBERTSHAW PILOT
Fig. 10: Honeywell and Robertshaw Pilots
9. Push in control knob all the way and hold in,
immediately light the pilot with a match. Continue
to hold control knob in for about one minute after
the pilot is lighted, release knob and it will pop
back up. Pilot should remain lighted. If it goes out,
repeat steps 4 through 8.
* If knob does not pop up when released, stop
and immediately call your service technician
or gas supplier.
* If the pilot does not stay lit after several tries,
turn the gas control knob to "OFF" and call
your service technician or gas supplier.
10. Stand to the side of the heater and turn the gas
control knob counter-clockwise to "ON".
11. Replace heater door.
12. Turn "ON" all electrical power to the heater.
13. Set the tankstat to the desired setting.
For Standing Pilot Model with
Honeywell Gas Valve, On/Off
Operation
1. STOP! Read the safety information.
2. Set the tankstat to the lowest setting.
3. Turn Off all electrical power to the heater.
4. Remove heater door panel.
5. Turn gas control knob clockwise to "OFF".
6. Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If you smell
gas, STOP! Follow "B" in the safety information
above on this label. If you don't smell gas, go to
the next step.
7. Locate pilot behind gas valve mounted on the
base panel of the burner drawer.
8. Turn knob on gas control counter-clockwise
to "PILOT".
9. Push down and hold the red reset button in, imme-
diately light the pilot with a match. Continue to hold
down red reset button for about one minute after
the pilot is lighted. Release red reset button and it
will pop back up. Pilot should remain lighted. If it
goes out, repeat steps 4 through 8.
GAS CONTROL
KNOB SHOWN
IN "OFF"
POSITION
GAS INLE
T
Fig. 11: Honeywell Gas Valve