Raypak 0133-4001 WH Electric Heater User Manual


 
INSTALLING THE VENT DAMPER VENT DAMPER GENERAL WIRING DIAGRAM
Fig. # 8183.0
Fig. # 8615.0
NO
YES
NO
YES
INSTALL VENT
DAMPER WITH
ACTUATOR TO
SIDES OF VENT
ONLY. DO NOT
MOUNT ABOVE OR
BELOW VENT.
TO CHIMNEYTO BOILER
D808
FLOW >
HORIZONTAL INSTALLATION
TO CHIMNEY
TO BOILER
D808
VERTICAL
INSTALLATION
ACTUATOR MAY BE
INSTALLED IN ANY
POSITION ON
VERTICAL PIPE.
VENT DAMPER
For safe, efficient operation, the vent damper and
all flue product carrying areas of the appliance must be
checked annually, with particular attention given to
deterioration from corrosion or other sources. Check
vent damper operation as follows:
1. When the heater is off, check that the vent
damper position indicator points to the closed
position, Fig. 4.
INSTALL THE VENT DAMPER TO SERVICE ONLY THE SINGLE APPLIANCE FOR WHICH IT IS INTENDED.
IF IMPROPERLY INSTALLED, A HAZARDOUS CONDITION, SUCH AS AN EXPLOSION OR CARBON
MONOXIDE POISONING, COULD RESULT.
Fig. # 8181.0
2. Turn the thermostat or controller up to call for heat
and check that the vent damper indicator points to
the open position, Fig. 4.
3. Turn the thermostat or controller down again and
check that the vent damper position indicator
returns to the closed position.
THE VENT DAMPER MUST BE INSPECTED AT
LEAST ONCE A YEAR BY A TRAINED,
EXPERIENCED SERVICE TECHNICIAN. THE
NAME OF THE PERSON WHO ORIGINALLY
INSTALLED YOUR VENT DAMPER IS SHOWN ON
THE INSTALLATION LABEL. DAMPER MUST BE IN
THE OPEN POSITION WHEN HEATER MAIN
BURNERS ARE OPERATING.
FIG. 4 - VENT DAMPER POSITON INDICATOR SHOWING OPEN & CLOSED POSITIONS.
Damper
Position
Indicator
DAMPER OPEN DAMPER CLOSED
Damper
Position
Indicator
16
HEATER
HEATER
Motor
End
Switch
C.
N.O. N.C.
1K2
1K1
R
1R
1K3
123
4
5
D808
Thermostat or
Controller
Dual Valve
Combination Gas
Control or
Ignition System
Optional Limit
LocationLimit
Transformer
L1
(Hot)
L2
1
1
Yellow Blue
Power supply provide disconnect me ans an overload protection as requ ired.
Black Orange Red
Power supply provide disconnect means an overload protection as required.