Quantum 150-08ACW-134 Water Heater User Manual


 
Owner’s Manual Quantum Energy Technologies
Document number: QDC0030PD-11 Page 36 of 40
A.11: Technical Data For Service Personnel – SIAM Compressors – R134a
Parameters 150-08ACW-134 270 & 340-11AC3-134
340TIH-134
340-17ACW-134
Superheat setting 1.5Turn(F.Close) 3.5 Turns(7 Turns ) F..Open 3.5Turns(7Turns) F.Open
TX valve + orifice size TI-E 2# TEN2 # 3(AAE 2MC) TEN2 # 4
Winding Resistance @20 C-R: 2.13, C-S: 3.91 C-R: 0.96, C-S: 1.77
Run Capacitor 30μF (+10, -5%) 370 VAC 30μF (+10, -5%) 370 VAC 60μF (+0, -15%) 400 VAC
Rated power supply 220-240VAC, 50Hz 220-240VAC, 50Hz 220-240VAC, 50Hz
Rated circuit breaker 1Φ, 15A 1Φ, 15A 1Φ, 15A
De-ice control setting On-5, Off + 8 (Timed De Icing) On - 5, Off + 8 (Timed De Icing) On-5, Off + 8 (Timed De Icing)
Liquid injection capillary Eyre: ID 1.1mm x 1.5m Eyre: ID 1.1mm x 2.9m ID 1.1mm x 2m
Liquid injection thermostat On at 85, Off at 75 On at 85, Off at 75 On at 85, Off at 75
Water temperature setting 55/5 (Del. 60) 55/5 (Del. 60) 55/5 (Del. 60)
Refrigerant charge 1650g 1850g 2650g
Thermal cut-out setting 105, manual reset 105, manual reset 105, manual reset