Quadra-Fire FG21SP-LP Indoor Fireplace User Manual


 
10 Quadra-Fire • Fogata Grande
A. Fuel
Beforemakinggasconnectionsensureappliancebeingin-
stallediscompatiblewiththeavailablegastype.
B. Gas Pressure
Properinputpressuresarerequiredforoptimumappliance
performance.Gaslinesizingrequirementsneedtobemade
followingNFPA51.
C. Gas Connection
Note: Havethegassupplylineinstalledin accordance
with localbuilding codes,if any.If not,followANSI
223.1.Installationshouldbedonebyaqualiedinstaller
approvedand/orlicensedasrequiredbythelocality.(In
theCommonwealthofMassachusettsinstallationmustbe
performedbyalicensedplumberorgastter.)
Note: A listed(andCommonwealthofMassachusetts
approved)1/2in.(13mm)T-handlemanualshut-offvalve
andexiblegas connectorareconnectedtothe1/2in.
(13mm)controlvalveinlet.
If substituting for these components, please consult
local codes for compliance.
5
Gas Information
WARNING
Fire Risk
Explosion Risk
• Gasbuild-up during line purgemay
ignite.
• Purgeshouldbeperformedbyqualied
technician.
• Ensureadequateventilation.
• Ensuretherearenoignitionsourcessuch
assparksoropenames.
Fire Risk
Explosion Risk
Verifyinletpressures.
• High pressure may cause overfire
condition.
• Lowpressuremaycauseexplosion.
• Verify minimumpressures when other
householdgasappliancesareoperating.
Installregulatorupstream of valve if line
pressureisgreaterthan1/2psig.
WARNING
Pressurerequirementsforapplianceareshownintablebe-
low.Minimumpressuresmustbemetwhenotherhousehold
gasappliancesareoperating.
Pressure Natural Gas Propane
MinimumInletPressure 5.0in.w.c. 11.0in.w.c.
MaximumInletPressure 7.0in.w.c. 14.0in.w.c.
• Incominggas lineshouldbepipedtothe1/2 in.
connection.
• Asmallamountofairwillbeinthegassupplylines.
Whenrstlightingapplianceitwilltakeashorttime
forairtopurgefromlines.Subsequentlightingofthe
logsetwillnotrequiresuchpurging.
WARNING
CHECK FOR GAS LEAKS
Fire Risk
Explosion Risk
Asphyxiation Risk
• Checkallttingsandconnections.
• Donotuseopename.
• Afterthegaslineinstallationiscomplete,
allconnectionsmustbetightenedand
checkedforleakswithacommercially
available,non-corrosive leakcheck
solution.Besuretorinseoffallleakcheck
solutionfollowingtesting.
Fittingsandconnectionsmayhaveloosened
duringshippingandhandling.