Polaris PC 130-50 2NV Water Heater User Manual


 
15
Do not use with piping that has been treated with
chromates, boiler seal or other chemicals and do not
add any chemicals to the water heater piping.
If the space heating system requires water temperatures
in excess of 120°F (48.9°C), a mixing valve (provided)
must be installed per the manufacturer’s instructions
in the potable hot water supply to limit the risk of scald
injury.
Pumps, valves, piping and fittings must be compatible
with potable water.
A properly installed flow control valve is required to pre-
vent thermosiphoning. Thermosiphoning is the result
of a continuous flow of water through the air handler
circuit during the off cycle. Weeping (blow off) of the
temperature and pressure relief valve (T & P) or higher
than normal water temperatures are the first signs of
thermosiphoning.
The hot water line from the water heater should be ver-
tical past any mixing valve or supply line to the heating
system to remove air bubbles from the system.
Do not connect the water heater to any system or
components previously used with non-potable water
heating appliances when used to supply potable water.
Storage Tank Installation
When installing the Polaris® with a storage tank, see figure
18 for piping suggestions.
Solar Installation
If this water heater is used as a solar storage heater or as
a backup for the solar system, the water supply tempera-
tures to the water heater tank may be in excess of 120°F
(48.9°C). A mixing valve must be installed in the water sup-
ply line to limit the supply temperature to 120°F (48.9°C).
Note: Solar water heating systems can often supply water
with temperatures exceeding 180°F (82.2°C) and may
result in water heater malfunction.
Figure 17: Air Handler Piping Installation
Mixing Valve
Metal Drain Pan
6” (15.2cm)
Air Gap Max.
Adequate Drain