10 How to Install
10.1. Before installing the air conditioner, please read the following:
10.1.1. Electrical Work.
•
Always use at the rated voltage and with a specific air conditioning circuit.
• Power supply point shall be the place where there is ease for the power disconnection in case of emergency.
•
Some installation locations may require installation of a short-circuit breaker.
• Time delay fuse or circuit breaker rating is 16 Ampere for CW-C170KR/CW-A170KR/CW-C200KR/CW-A200KR and 20
Ampere for CW-C240KR/CW-A240KR.
•
Nominal cross sectional area of power supply wire must be 3 core x 2.5 mm
2
or above.
•
The power supply must be from an independent circuit.
•
All electrical installations must be made in accordance with local wiring and safety regulations wherever applicable.
• There must be a double pole switch with minimum of 3 mm contact gap in the fixed installation circuit.
10.1.2. Select the Best Location.
•
Install the unit at the nearest power outlet.
•
The air conditioner should be installed in a dry place where there are no draughts.
• Condensation from the air conditioner must be drained into an appropriate location.
• Do not install in a location where flammable gas leaks is a possibility.
•
Usage in locations where the air is salty such as coastal areas or near hot spas, or where sulphurous gas is generated, may
lead to a malfunction.
• Do not install this appliance in a laundry room or other locations where water may drip from the ceiling, etc.
• Select an installation location which is rigid and strong enough to support or hold the unit and select a location for easy
maintenance.
10.2. Preparation for Installation.
•
There should not be any obstacles surrounding the unit.
• Prepare an installation hole that is only slightly bigger than the cabinet size.
16
CW-C170KR / CW-C200KR / CW-C240KR / CW-A170KR / CW-A200KR / CW-A240KR