Panasonic CU-S24NKUA Air Conditioner User Manual


 
33
12.5 Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
If compressor discharge temperature exceeds 233.6°F, compressor will be stopped, occurs 4 times per 20
minutes, timer LED will be blinking. “F97” is indicated.
12.6 Low Pressure Protection Control (Gas Leakage Detection)
Control start conditions
o For 5 minutes, the compressor continously operates and outdoor total current is between 0.81A and 1.23A.
o During Cooling and Soft Dry operation:
Indoor suction temperature – indoor piping temperature is below 7.2°F
Control contents
o Compressor stops (and restart after 3 minutes).
o If the conditions above happened 2 times within 20 minutes, the unit will:
Stop operation
Timer LED blinks and “F91” indicated.
12.7 Low Frequency Protection Control 1
When the compressor operates at frequency lower than 25Hz continued for 240 minutes, the operation frequency
will be change to 24Hz for 2 minutes.
12.8 Low Frequency Protection Control 2
When all below conditions comply, minimum limit of compressor frequency will be set.
Temperature, T, for: Cooling / Soft Dry
Indoor intake air (°F) T < 57.2 or 86
Outdoor air (°F) T < 55.4 or T 100.4
Indoor heat exchanger (°F) T < 86
12.9 Outdoor Air Temperature Control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
This control will begin 1 minute after the compressor starts.
Compressor frequency will adjust based on outdoor air temperature.
Free
Limited Frequency
Outdoor air temperature
100.4°F or 77°F
98.6°F or 71.6°F