Napoleon Fireplaces GVFS60-N Indoor Fireplace User Manual


 
14
W415-0204 / C / 10.02.01
TEST SOLUTION
PROBLEMSYMPTOM
Pilot goes out
while standing;
Main burner is in
'OFF' position.
Gas piping is undersized. - turn on all gas appliances and see if pilot flame flutters, dimin-
ishes or extinguishes, especially when main burner ignites. Monitor
appliance supply working pressure.
- check if supply piping size is to code. Correct all undersized piping.
Flames are con-
sistently too large
or too small.
Carboning occurs.
- check pressure readings:
Inlet pressure can be checked by turning screw (A) counter-clock-
wise 2 or 3 turns and then placing pressure gauge tubing over the
test point. Check with burner operating on "HI". Gauge should read
7" (minimum 4.5") water column for natural gas or 13" (11" mini-
mum) water column for propane.
Outlet pressure can be checked the same as above using screw
(B). Check with burner operating on "HI". Gauge should read 3.5"
water column for natural gas or 10" water column for propane.
AFTER TAKING PRESSURE READINGS, BE SURE TO TURN
SCREWS CLOCKWISE FIRMLY TO RESEAL. DO NOT OVERTORQUE.
Leak test with a soap and water solution.
Unit is over-fired or under-
fired.
P
I
AB
P
I
L
O
T
N
O
L
O
T
H
I
L
O
F
F
O
Remote wall
switch is in "OFF"
position; main
burner comes on
when gas knob is
turned to "ON" po-
sition.
Wall switch is mounted up-
side down
- reverse.
Faulty valve.
- replace.
- replace.Remote wall switch is
grounding.
- check for ground (short); repair ground or replace wire.Remote wall switch wire is
grounding.
Carbon is being
deposited on logs
or combustion
chamber surfaces.
Air shutter has become
blocked
- ensure air shutter opening is free of lint or other obstructions.
Flame is impinging on the
logs or combustion cham-
ber.
- check that the logs are correctly positioned.
- open air shutter to increase the primary air. See air shutter open-
ings, page 15.
- check the input rate: check the manifold pressure and orifice size
as specified by the rating plate values.
Flame is impinging on the
logs or combustion cham-
ber.
- check that the logs are correctly positioned.
- open air shutter to increase the primary air. See air shutter open-
ings, page 15.
- check the input rate: check the manifold pressure and orifice size
as specified by the rating plate values.
Exhaust fumes
smelled in room,
headaches.
- increase fresh air supply. (Use one of the methods described in
ANSI Z223.1 Section 5.3 or the applicable local code.)
Not enough combustion air.
- increase fresh air supply. (Use one of the methods described in
ANSI Z223.1 Section 5.3 or the applicable local code.)
Not enough ventilation air.