INSTALLATION WHEN
INSTALLED WITH BLOWER
KIT EP63
For reduced clearances installation must comply with
NFPA 211or CAN/CSA-B365.
Alcove installation
Model 1600C-1 may be installed into an alcove having a
depth of not more than 4 feet and a height of at least 7 feet,
when using a listed double wall connector that is rated for a
minimum 12” clearance to combustible material.
The minimum clearances are as shown.
Stove installation
If the stove is to be installed on a
combustible floor, it must be
placed on a approved
non-combustible hearth pad,
that extends 8" (200mm)
beyond the stove sides and
back, and 18" (455mm) to the
front.
Listed single wall chimney connector
Flue configuration
Type 1 Horizontal Vertical
FROM
UNIT
A 16” 16”
B* 10” 16”
C11”11”
FROM
PIPE
D 25” 25”
E ... 18”
F ... 18”
* A 18 in. Minimum clearance should be maintained
from combustible wall to the chimney connector.
Double walled connectors listed for a minimum
clearance of 12” or less from combustible materials
must be used to achieve the following clearances.
Flue configuration
Type 2 Horizontal Vertical
FROM
UNIT
A 16” 16”
B 10” 10”
C11”11”
FROM
PIPE
D 25” 25”
E ... 16”
F ... 12”
6
1 6 "
1 6 "
1 6 "
4 f o o t m a x
8 "
1 8 "
8 "
8 "
A
B
F
D
E
C
C
8 4 "
Illu stra ted w ith .7 5" h e arth pa d .
Alcove installation
Walls shall not extend from front of unit when installed
in the alcove configuration.