Multiquip S-500 Water Pump User Manual


 
PAGE 16 S-500 SERIES SUBMERSIBLE PUMPS OPERATION & PARTS MANUAL REV. #0 (10/01/04)
S-500 SERIES SUB. PUMP CONTROL BOX INSTALLATION
The S-500 series submersible
pumps are also designed to work
with a control box (
Model CB3
). This
control box contains the necessary
electronics (float switch connections) to operate the pump.
Remember this control box contains hazardous voltages.
Disconnect all sources of power before installing or
servicing. There exists the possibility of electrocution,
electric shock or burn, which can cause severe bodily
harm or even
death
!
This control box should only be installed or serviced by a
licensed electrician or qualified personnel
.
Control Box Mounting
Mount the control box in an
upright vertical position
. Make sure
the control box is securely fastened to a flat surface, that is free
of dust, dirt, moisture or any elements that may contaminate or
erode the electronic components of the control box.
Single-Phase Power Installation (Input)
All S-500 series submersible pumps require 115 V, 60 Hz.,
single-phase power for
normal operation
.
If you cannot determine what your pump's power
requirements are, look at the vendor supplied identification
name tag attached to the pump or please contact Multiquip's
Service/Technical Assistance department.
Applying incorrect power (
voltage phasing
) to the
submersible pump can cause severe damage to the pump.
Please make sure that the correct voltage and phase are
transferred to the pump at all times.
Power Cord Requirements
When routing the 115 VAC, 60 Hz., single phase power via a
power cord to the control box,
ALWAYS
use the correct wire size.
Please reference Table 4 below (Cord Length/Wire Size) to
determine the correct wire size. Incorrect wire size can adversely
affect the performance of the pump.
Connecting Dual float Switch (SW-1WOP) To Control Box
1. Remove the float switch input connector housing, then
route the float switch wires through the cable gland on the
control box. Attach the wires of the float switch to the
terminal block as indicated by Table 5 and Figure 6.
2. Tighten the connector housing to ensure a tight fit between
the cord and the connector body. This will prevent the cable
from pulling out of the terminal block and also prevent
moisture from entering the control box.
3. Determine the length of the float switch wires, then secure
float switch wires to pump discharge hose. See Figures 3
and 6 and Table 3 to determine the pumping range.
EZISERIWDNAHTGNELDROC.4ELBAT S
SPMA.TF05.TF001.TF051
6GWA61GWA61GWA41
8GWA61GWA41GWA21
01GWA61GWA41GWA21
21GWA41GWA41GWA21
41GWA41GWA21GWA01
61GWA21GWA21GWA01
SNOITCENNOCHCTIWSTAOLF.5ELBAT S
HCTIWSTAOLF
KCOLBLANIMRET
REBMUN
TRATS
)KCALB(1LANIMRET
)ETIHW(2LANIMRET
POTS
)ETIHW(7LANIMRET
)KCALB(8LANIMRET