SS38 Direct Vent Gas Stove
Figure 40
A listed manual shutoff valve must be installed upstream of
the appliance. Union tee and plugged 1/8" NPT pressure
tapping point should be installed upstream of the appliance.
Figure 28
Install main gas valve (equipment shutoff valve)
in an accessible location. The main gas valve is for turning on
or shutting off the gas to the stove.
Check your building codes for any special requirements for locating equipment shutoff valve to
stoves.
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe.
Excess sealant in pipe could result in clogged burner system valves.
We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 28. Locate
sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply
and burner system. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment
trap collects moisture and contaminants and keeps them from going into the burner system gas controls.
If sediment trap/drip leg is not installed or is installed wrong, burner system may not run properly.
3" Minimum
FP1978
gas connection
Pipe Nipple
Cap
Figure 28 -
Gas Connection
Tee Joint
Approved
Flexible
Gas Line
CSA Design-Certified Equipment Shutoff Valve
with 1/8" NPT Tap*
Sediment Trap/Drip Leg
From Gas Meter
(5.0" w.c. to 10.5" w.c. Pressure)
From External Regulator
(11" w.c. to 13" w.c. Pressure)