Monessen Hearth LCUF32-F Indoor Fireplace User Manual


 
10 26D4721
FIREBOX FRAMING
H
G
D
F
E
A
C
B
A
1
/2"or
5
/8"
C
A
G
C
G
A
Firebox framing can be built before or after the appliance is set in place. Construct rebox framing following Figures 9
through 12 and the chart below for your speci c installation requirements. See Figure 1 on Page 6 for rebox dimensions.
The framing headers may rest on the top of the rebox standoffs.
The rebox may be installed directly on a combustible oor or raised on a platform of an appropriate height. When the
rebox is installed directly on carpeting, tile, or other combustible material, other than wood ooring, the rebox shall be
installed on a metal or wood panel extending the full width and depth of the enclosure.
The classi cation "noncombustible material" includes, but is not limited to: stone, brick, and mortar. Noncombustibles are
safe to overlay the black-painted metal face, including radiant plates, and do not pose a re hazard. Any noncombustible
nish material must not extend past or interfere with the replace opening.
The classi cation "combustible material" incudes, but is not limited to: plywood, drywall, and particle board. Combustible
materials may contact the sides, bottom, or back of the rebox. Do not overlay the black painted face with combustible
matierals.
Figure 9 - Corner Installation
Figure 11 - Stud Location
Figure 10 - Inside Chase Installation
Figure 12 - Recessed Installation
LCUF32-F
LCUF36C-R
A 37" 41¼"
B 34½" 37¾"
C 29" 32"
D 14" 16"
E 61¾" 68"
F 30" 34½"
G 16" 18"
H 43¾" 48¾"
Do not ll spaces around rebox with insulation or other materials. This could cause
a re.
WARNING
½" or "