Monessen Hearth CWC500 Indoor Fireplace User Manual


 
16
CWC Series Woodburning Fireplace
87D1504
COMMON MATERIALS AND FACTORS
MATERIAL K*
R
MINIMUM
THICKNESS
EH2416
Common Brick
0.458
5.0
1.09 0.50 in.**
0.10 5.46 in.**
(MHSC)
R Value is for 1/2 inch.
* Units of K = BTU/SQ FT/HR/˚F/IN
** Thickness of Listed Material
FP533ADD
Addendum
6/1/99 djt
8/4/99 changed .2 to .1
one inch to 1/2 inch djt
 Hearth extension material factors.
FP533ADD
NEW K of new material (per inch) thickness
required = ------------------------------------ X of listed
thickness K of listed material (per inch) material


To determine the thickness required for any  mate-
rial:

T (new) = 5.0 / 0.458 x 0.50 in. =  (new re-
quired thickness).
FP550
BR/BC - SEALING
DETAILS
9/29/97
Wall Covering
Noncombustible
Decorative
Facing
Noncombustible
Decorative
Covering
Seal all cracks
between fireplace
surround and wall
materials with
noncombustible
material.
Seal crack
between fireplace
and hearth extension
with noncombustible
material.
2x4" Header -
Do not notch at
standoffs.
Safety Strips -
Must be overlapped
Z\x" minimum.
Hearth Extension
Insulation
Side View
FP550
 Sealing gaps.