Monessen Hearth BUF400 Indoor Fireplace User Manual


 
16 61D1013
8'max.
FOR USE OF OPTIONAL AK-4 OUTSIDE AIR KIT
COMBUSTION AIR
1. Locate combustion air assembly at an exterior location which is not likely to be accidentally blocked in any manner.
Locate assembly a min. of 12" above the snow line to prevent blockage by snow accumulation.
2. Never mount the combustion air inlet assembly in a garage or storage area where combustible fumes such as gasoline
might be drawn into the replace.
3. Combustion air can be drawn from the crawl space under a house when an adequate supply of air is provided by open
ventilation.
4. CAUTION: Do not take combustion air from attic space or garage space.
5. Locate air supply inlet at least 3' away from any appliance vent terminal.
6. Avoid extremely long runs and numerous turns in the duct leading from the replace to the combustion air assembly.
These conditions increase the resistance to the free ow of air through the duct. See Figures 14 through 17 for methods
of installing the outside air for combustion assemblies.
Figure 14 - Basement Installation
Figure 15 - Concrete Slab Installation
(Optional Outside Air Runs)
Above
Snow
Level
Ground
Level
Basement
Wall
Inlet Grill in
Sof t
(Overhang)
Figure 17 - 45° Corner Installation on
Slab Floor
Figure 16 - Installation Above Basement or
Crawl Space
Inside Wall
Outside
Wall
Duct Extended
to Miss Joist
To Outside Wall
Note: Fireplace model in illustrations may not be representative of your appliance.