Mitsubishi P288T(Y)SJMU-A PUHY-P312 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 152 -
HWE09120 GB
Operation
Outdoor unit model
PUHY-P360TSJMU-A
PUHY-
P96TJMU-A
PUHY-
P120TJMU-A
PUHY-
P144TJMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/ - [70°F/ - ]
Outdoor
8.3°C/6.1°C [47°F/43°F]
Indoor
unit
No. of connected
units
Unit
7
No. of units in opera-
tion 7
Model - 48/48/48/54/54/54/54
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe 10 [32-3/4 ]
Total pipe length 75 [246-1/16]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz] 33 [72]
Outdoor
unit
Electric current A 92.0
Voltage V 230
Compressor frequency Hz 71 81 102
LEV open-
ing
Indoor unit
Pulse
332/332/332/406/406/406/406
SC (LEV1) 0
LEV2 2100 2100 2100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi]
2.76/0.63 2.76/0.63 2.76/0.63
[401/92] [401/92] [401/92]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
75 [167] 70 [158] 89 [192]
Heat exchanger out-
let (TH3) -2 [28] -1 [30] -3 [27]
Accumulator inlet -2 [28] -1 [30] -3 [27]
Accumulator outlet -2 [28] -1 [30] -3 [27]
Compressor inlet -2 [28] -1 [30] -3 [27]
Compressor shell
bottom 40 [104] 40 [104] 40 [104]
Indoor
unit
LEV inlet 37 [98] 37 [98] 37 [98]
Heat exchanger
inlet 74 [165] 74 [165] 74 [165]