Mitsubishi Electronics PUZ-A18NHA2-BS Air Conditioner User Manual


 
43
A6
(6606)
Communication error with communica-
tion processor
Defective communication between unit
processor and transmission processor
Note) The address and attribute display at
remote controller indicate the con-
troller that detected abnormality.
1 Data of transmission proces-
sor or unit processor is not
transmitted normally because
of accidental trouble such as
noise or thunder surge.
2 Address forwarding from unit
processor is not transmitted
normally because of defective
transmission processor hard-
ware.
Turn off the power supply of outdoor unit and
indoor unit and FRESH MASTER or LOSSNAY
at the same time for 2 minutes or more, and
turn the power on again. System returns to nor-
mal if abnormality was accidental malfunction.
If the same abnormality generates again,
abnormality-generated controller may be defec-
tive.
Continued to the next page.
Error Code
Abnormal point and detection method
Case Judgment and action
A7
(6607)
NO ACK signal
1. Transmitting side controller detects
abnormal if a massage was transmitted
but there is no reply (ACK) that a mes-
sage was received. Transmitting side
detects abnormality every 30 seconds, 6
times continuously.
Note) The address and attribute displayed
at remote controller is indicate the
controller that did not reply (ACK).
Common factor that has no rela-
tion with abnormality source.
1 The unit of former address
does not exist as address
switch has changed while the
unit was energized.
2 Extinction of transmission wire
voltage and signal is caused by
over-range transmission wire.
• Maximum distance ······200m
[656ft]
Remote controller line
··(12m
[39ft])
3 Extinction of transmission wire
voltage and signal is caused by
type-unmatched transmission
wire.
Type ······
With shield wire-
CVVS, CPEVS
With normal wire (no shield)-
VCTF, VCTFK, CVV
CVS, VVR, VVF, VCT
Diameter····1.25mm
2
[AWG16]
or more
4 Extinction of transmission wire
voltage and signal is caused
by over-numbered units.
5 Accidental malfunction of
abnormality-detected controller
(noise, thunder surge)
6 Defective of abnormality gen-
erated controller
2. If displayed address or attribute is out-
door unit, Indoor unit detects abnormali-
ty when indoor unit transmitted to out-
door unit and there was no reply (ACK).
1 Contact failure of transmission
wire of outdoor unit or indoor
unit
2 Disconnection of transmission
connector (CN2M) of outdoor
unit
3 Defective transmitting receiv-
ing circuit of outdoor unit or
indoor unit
Always try the followings when the error
“A7” occurs.
1 Turn off the power supply of outdoor unit and
indoor unit and FRESH MASTER or LOSS-
NAY at the same time for 2 minutes or more,
and turn the power on again. If malfunction
was accidental, the unit returns to normal.
2 Check address switch of abnormality gener-
ated address.
3 Check disconnection or looseness of abnor-
mality generated or abnormality detected
transmission wire (terminal block and con-
nector)
4 Check if tolerance range of transmission wire
is not exceeded.
5 Check if type of transmission wire is correct
or not.
If there were some troubles of 1-5 above,
repair the defective, then turn off the power
supply of outdoor unit and indoor unit and
FRESH MASTER or LOSSNAY at the same
time for 2 minutes or more, and turn the power
on again.
• If there was no trouble with 1-5 above in sin-
gle refrigerant system (one outdoor unit), con-
troller of displayed address or attribute is
defective.
• If there was no trouble with 1-5 above in dif-
ferent refrigerant system (2 or more outdoor
units), judge with 6.
6 If address of abnormality source is the
address that should not exist, there is the
unit that memorizes nonexistent address
information. Delete useless address informa-
tion with manual setting function of remote
controller.
Only the system FRESH MASTER or LOSS-
NAY are connected to, or the system that is
equipped with group setting of different
refrigerant system.
If there was no trouble with 1-6 above,
replace the controller board of displayed
address or attribute.
If the unit does not return to normal, multi-con-
troller board of outdoor unit may be defective
(repeater circuit).
Replace multi-controller board one by one to
check if the unit returns to normal.
3. If displayed address or attribute is
indoor unit, remote controller detects
abnormality when remote controller
transmitted to indoor unit and there was
no reply (ACK).
1 During group operation with
indoor unit of multi- refrigerant
system, if remote controller
transmit to indoor unit while
outdoor unit power supply of
one refrigerant system is
turned off or within 2 minutes
of restart, abnormality is
detected.
2 Contact failure of transmission
wire of remote controller or
indoor unit
3 Disconnection of transmission
connector (CN2M) of indoor
unit
4 Defective transmitting receiv-
ing circuit of indoor unit or
remote controller
OCH429--2.qxp 07.11.20 9:18 AM Page 43