Mitsubishi Electronics PUZ-A18NHA2-BS Air Conditioner User Manual


 
35
10-4. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is turned on>
(Note 1) Refer to indoor unit section for code P and code E.
Error Code
Abnormal point and detection method
Case
Judgment and action
None
1 No voltage is supplied to terminal
block(TB1) of outdoor unit.
a) Power supply breaker is
turned off.
b) Contact failure or discon-
nection of power supply
terminal
c) Open phase (L1 or L2
phase)
2 Electric power is not charged
to power supply terminal of
outdoor power circuit board.
a) Contact failure of power
supply terminal
b) Open phase on the outdoor
power circuit board
A12-A24N :Disconnection of
connector R or S
A30-A42N :Disconnection of
connector TABT or TABS
3 Electric power is not supplied to
outdoor controller circuit board.
a) Disconnection of connector
(CNDC)
4 Disconnection of reactor (DCL
or ACL)
5 Disconnection of outdoor noise
filter circuit board or parts failure
in outdoor noise filter circuit
board
As for A30-A42N type, it is
especially needed to check the
resistance RS1 on the noise
fiter circuit board.
6 Defective outdoor power circuit
board
7 Defective outdoor controller
circuit board
1 Check following items.
a) Power supply breaker
b) Connection of power supply terminal block
(TB1)
c) Connection of power supply terminal block
(TB1)
2 Check following items.
a) Connection of power supply terminal block
(TB1)
b) Connection of terminal on outdoor power
circuit board
A12-A24N: Disconnection of connector R or S
Refer to 10-9.
A30-A42N: Disconnection of connector TABT
or TABS Refer to 10-9.
3 Check connection of the connector (CNDC)
on the outdoor controller circuit board.
Check connection of the connector, LD1 and
LD2 for A12-A24N and CNDC for A30-A36N,
on the outdoor power circuit board. Refer to
10-9.
4 Check connection of reactor. (DCL or ACL)
A12-A24N: Check connection of “LO” and
“NO” on the outdoor noise filter circuit board.
Check connection of “R” and “S” on the
outdoor power circuit board.
A30-A42N: Check connection of “L1” and “L2”
on the active filter module.(ACTM)
Refer to 10-9.
5 a) Check connection of outdoor noise filter
circuit board.
b) Replace outdoor noise filter circuit board.
Refer to 10-9.
6 Replace outdoor power circuit board.
7 Replace controller board (When items above
are checked but the units cannot be repaired).
F3
(5202)
63L connector open
Abnormal if 63L connector circuit is open
for 3 minutes continuously after power sup-
ply.
63L: Low-pressure switch
<A42N only>
1 Disconnection or contact failure
of 63L connector on outdoor
controller circuit board
2 Disconnection or contact failure
of 63L
3 63L is working due to refriger-
ant leakage or defective parts.
4 Defective outdoor controller
circuit board
1 Check connection of 63L connector on
outdoor controller circuit board.
Refer to 10-9.
2 Check the 63L side of connecting wire.
3 Check refrigerant pressure.
Charge additional refrigerant.
Check continuity by tester.
Replace the parts if the parts are defective.
4 Replace outdoor controller circuit board.
OCH429--2.qxp 07.11.20 9:18 AM Page 35