Mitsubishi Electronics PURY-P216TSKMU-A Air Conditioner User Manual


 
Specications are subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
Outdoor Unit: PURY-P216TSKMU-A (-BS) – DIMENSIONS
Intake
air
Intake
air
Intake
air
Discharge air
Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2.Twinning pipe (High pressure) should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3.The pipe section before the Twinning pipe (section "a" in the figure) must have at least 500mm(19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4.Only use the Twinning pipe by Mitsubishi (optional parts).
5.Connect the outdoor unit 1 with the Twinning pipe (Low pressure) (section "d" in the figure).
P96
Twinning Kit
~Outdoor unit
P120
High pressure
fd
e19.05(3/4)
ø22.2(7/8)
Component
unit model
Unit model
Low pressure
(Note 5)
-
ø19.05(3/4)
P216
CMY-R100XLCBK
Low pressure
Twinning pipe connection size
Outdoor unit 1
Component unit name
Package unit name
BC controller~Twinning pipe
a
b
High pressure
Outdoor Twinning Kit(optional parts)
Outdoor unit 2
PURY-P216TSKMU-A(-BS)
PURY-P120TKMU-A(-BS)
PURY-P96TKMU-A(-BS)
ø28.58(1-1/8)
ø28.58(1-1/8)
Outdoor unit 1
Outdoor unit 2
Front view
Left view
To BC controller
To BC controller
a
b
e
f
c
d
Twinning pipe(High pressure)
<optional parts>
Twinning pipe(Low pressure)
<optional parts>
30(1-3/16)740(29-5/32)
1750(68-29/32)
1650(64-31/32)
1220(48-1/16)
PURY-P216TSKMU-A(-BS)
Unit : mm(in.)