Mitsubishi Electronics PMFY-P08NBMU-E Air Conditioner User Manual


 
16
Control modes
Control details
Set by remote controller.
2. Drain pump
Remarks
1. Fan
Type
Fan speed notch
4 speeds type [Low], [Medium2], [Medium1], [High]
3. Vane
(up/ down vane change)
2-1. Drain pump control
The drain pump turns ON for the specified amount of time when any of the
following conditions is satisfied:
1 ON for 3 minutes after the operation mode is switched from COOL or DRY to
another operation mode (FAN).
2 ON for 6 minutes after the drain sensor is determined to be submerged
using the liquid level detection method given below.
3 ON for 6 minutes after indoor piping (liquid piping) temperature – indoor
room temperature [ -18°F, AND the drain sensor input is at the short or
open level.
(If condition 2 or 3 is still being met after the drain pump has been turned ON
for 6 minutes, the drain pump is kept ON for a further 6 minutes.)
2-2. Liquid level detection method
The liquid level is detected by determining whether or not the drain sensor is
submerged, based on the amount the temperature rises after self-heating the
sensor. This process is performed if any of the following conditions is satisfied:
1 Drain pump is ON.
2 Indoor piping (liquid piping) temperature – indoor room temperature [ -18°F
3 Indoor piping (liquid piping) temperature or indoor room temperature is at
the short or open level temperature.
4 Every 1 hour after the drain pump has been switched from ON to OFF.
Same as the control performed during the COOL operation, but with no restriction
on the vane's downward blow setting.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
8-3. FAN OPERATION
<How to operate>
1 Press POWER ON/OFF button.
2 Press the operation MODE button to display FAN.
OC341B--1.qxp 07.7.11 1:29 PM Page 16