Mitsubishi Electronics P500YMF-C Air Conditioner User Manual


 
96
6
6
5
4
3
2
1
5
4
3
2
1
2
5
1
3
4
6
Brown
Red
Blue
Orange
Yellow
White
Brown
Red
Blue
Orange
Yellow
White
To
LEV
10k LED
(Self-diagnostic monitor)
Measured Data Signal OUTDOOR MAIN board SW1 Setting
LEV1 pulse
LEV 3 pulse
LEV 3a pulse
BC controller bypass
output superheat
BC controller
intermediate subcool
BC controller liquid
subcool
(Solenoid Valve Troubleshooting Flow)
SH12
SC16
SC11
Start
Visually check for disconnection between connec-
tors and terminals, and confirm correct lead colors.
Intermediate
connector
Controller
board
Remove connectors from the board and
use a tester to check conduction.
Check between connectors 1-3-5 and 2-
4-6.
Use a tester to measure resistance
between each coil (red-white, red-orange,
brown-yellow, brown-blue).
Correct value is: 150Ω±10%
Adjust, repair.
Check for the following:
LEV full open: ticking sound
LEV full closed: no sound
Change LEV
OK?
Confirm if LEV is closed fully.
Attach check LEDs
illustrated nearby to board
connectors and confirm
that LEDs light for 10
seconds.
Change the
board.
1
ON
2345678910
1
ON
2345678910
1
ON
2345678910
1
ON
2345678910
1
ON
2345678910
OK?
OK?
Change LEV
Correction.
OK?
OK?
Change LEV
OK?
End
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
1
ON
2345678910