Mitsubishi Electronics P240Y(T)SHMU-A Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 170 -
HWE0803A GB
Operation
Outdoor unit model
PURY-P216TSHMU-A
PURY-P120THMU-A PURY-P96THMU-A
Model name of BC controller CMB-P1013NU-GA
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor 35°C/- [95°F/-]
Indoor unit
No. of connected units
Unit
6
No. of units in operation 6
Model - 36/36/36/36/36/36
Piping
Main pipe
m
[ft]
5[16-3/8"]
Branch pipe 10 [32-3/4"]
Total pipe length 65 [213-1/4"]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz]
43.0 [95]
Outdoor
unit
Electric current A 53.8
Voltage V 230
Compressor frequency Hz 75 65
LEV open-
ing
Indoor unit
Pulse
275/275/275/275/275/275
BC controller (1/2/3) 2000/2000/280
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.82/0.91
[409/131]
2.66/0.91
[385/131]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.66/2.66
[385/385]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
82 [180] 85 [185]
Heat exchanger outlet
(TH3)
43 [109] 39 [102]
Accumulator inlet 8 [46] 8 [46]
Accumulator outlet 8 [46] 8 [46]
Compressor inlet 20 [68] 19 [66]
Compressor shell bottom 42 [108] 40 [104]
Indoor unit
LEV inlet 22 [72]
Heat exchanger inlet 9 [48]