[ VIII Test Run Mode ]
- 175 -
HWE0803A GB
Operation
Outdoor unit model
PURY-P216TSHMU-A
PURY-P120THMU-A PURY-P96THMU-A
Model name of BC controller CMB-P1013NU-GA
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/- [70°F/-]
Outdoor 8.3°C/6.1°C [47°F/43°F]
Indoor unit
No. of connected units
Unit
6
No. of units in operation 6
Model - 36/36/36/36/36/36
Piping
Main pipe
m
[ft]
5 [16-3/18"]
Branch pipe 10 [32-3/4"]
Total pipe length 65 [213-1/4"]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz]
43.0 [95]
Outdoor
unit
Electric current A 54.0
Voltage V 230
Compressor frequency Hz 81 71
LEV open-
ing
Indoor unit
Pulse
350/350/350/350/350/350
BC controller (1/2/3) 110/110/1120
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.62/0.64
[380/92]
2.62/0.68
[380/98]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.60/2.27
[377/329]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
73 [163] 80 [176]
Heat exchanger outlet
(TH6)
2 [36] 0 [32]
Accumulator inlet -1 [30] -2 [28]
Accumulator outlet -1 [30] -3 [27]
Compressor inlet -1 [30] -3 [27]
Compressor shell bottom 40 [104] 40 [104]
Indoor unit
LEV inlet 33 [91]
Heat exchanger inlet 68 [154]