Mitsubishi Electronics P168 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 171 -
HWE0803A GB
Operation
Outdoor unit model
PURY-P240TSHMU-A
PURY-P120THMU-A PURY-P120THMU-A
Model name of BC controller CMB-P1013NU-GA
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor 35°C/- [95°F/-]
Indoor unit
No. of connected units
Unit
7
No. of units in operation 7
Model - 24/36/36/36/36/36/36
Piping
Main pipe
m
[ft]
5[16-3/8"]
Branch pipe 10 [32-3/4"]
Total pipe length 75 [229-5/8"]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz]
44.6 [98]
Outdoor
unit
Electric current A 60.2
Voltage V 230
Compressor frequency Hz 75 75
LEV open-
ing
Indoor unit
Pulse
200/275/275/275/275/275/275
BC controller (1/2/3) 2000/2000/290
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.82/0.89
[409/129]
2.82/0.89
[409/129]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.73/2.73
[395/395]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
82 [180] 82 [180]
Heat exchanger outlet
(TH3)
43 [109] 43 [109]
Accumulator inlet 8 [46] 8 [46]
Accumulator outlet 8 [46] 8 [46]
Compressor inlet 20 [68] 20 [68]
Compressor shell bottom 42 [108] 42 [108]
Indoor unit
LEV inlet 22 [72]
Heat exchanger inlet 11 [52]