Mitsubishi Electronics MXZ-2A20NA Air Conditioner User Manual


 
5
2. OUTDOOR UNIT INSTALLATION
2-1. CONNECTING WIRES FOR OUTDOOR UNIT
Be sure to use special circuits for room air conditioner.
Wiring work should be based on applicable technical standards.
Wiring connections should be made following the diagram.
• Screwsshouldbetightenedsotheywon’tloosen.
ELECTRICAL SPECIFICATIONS
OUTDOOR UNIT
MXZ-2A20NA
Powersupply(V,PHASE,Hz) 208/230, 1, 60
Max.Fusesize(timedelay)(A)
20
Min.CircuitAmpacity(A)
15
Fanmotor(F.L.A)
0.96
Compressor
(R.L.A) 10.1
(L.R.A) 15
Control voltage
Indoorunit-Remotecontroller:(Wireless)
Indoor unit-Outdoor unit : DC12-24V
1)Removetheservicepanel.
2)Fixtheconduitconnectortoconduitcoverwithlocknutthensecureit
against unit with screws.
3)Fixtheconduitcovertotheoutdoorunitthensecureitwithscrews.
4)Connectpowersupplycordandindoor/outdoorconnectingwiretotheter
-
minal block.
(Leavesomeslackinwirestoalloweasierservicing.)
5)Closetheservicepanelsecurely.Makesurethat3-2.PIPECONNECTION
is completed.
Remark:
* A disconnect switch should be required. Check the local code.
** Use a ring tongue terminal in order to connect a ground wire to terminal.
INDOOR UNIT A
Terminal block
Grounding
terminal **
INDOOR UNIT B
Terminal block
Grounding
terminal **
208/230 V AC
1phase 60 Hz
208/230 V AC
1phase 60 Hz
Grounding
terminal **
Grounding
terminal **
Terminal
block 1
Ground
OUTDOOR UNIT
Powersupply208/230VAC
1phase 2wires 60 Hz
Terminal block
UNIT A
Terminal block
UNIT B
Disconnect
switch *
Disconnect
switch *
Connect wires to the matching numbers of terminals.
CONNECTING WIRES AND CONNECTING GROUND WIRE
Use solid conductor AWG14 or stranded conductor AWG14.
Use double insulated copper wire with 600 V insulation.
• Usecopperconductorsonly.
* Follow local electrical code.
POWER SUPPLY CABLE AND GROUND WIRE
Use solid or stranded conductor AWG14.
• Usecopperconductorsonly.
* Follow local electrical code.
WARNING:
Usetheindoor/outdoorunitconnectingwirethatmeetstheStandardstoconnecttheindoorandoutdoorunitsandxthewiretotheterminal
blocksecurelysothatnoexternalforceisconveyedtotheconnectingsectionoftheterminalblock.Anincompleteconnectionorxingofthe
wirecouldresultinare.
For future servicing, give extra length to the connecting wires.
Grounding terminal
Conduit
cover
Lock nut
Connector