Mitsubishi Electronics BAC-HD150 Air Conditioner User Manual


 
- 4 -
1-1. Product Specifications
1-2. External dimensions
1 Specifications
Items Spec
Power source
Rated input 100-240 VAC ±10 % 0.4-0.3 A 50/60 Hz
Fuse 250 VAC 3.15 A Time-delay type (IEC127-2 S.S.5)
Interface
Rated output of the power supply
to M-NET transmission lines
22-30 VDC
LAN 10Base-T or 100Base-TX (LAN2 is for future use.)
Ambient
conditions
Temperature
Operating
temperature range
-10 ~ 55°C (14 ~ 131°F)
Storage
temperature range
-20 ~ 60°C (-4 ~ 140°F)
Humidity 30 ~ 90 %RH (Non-condensing)
Dimensions
266 (H) × 250 (W) × 97.2 (D) mm (10-
1
/2 (H) × 9-
7
/8 (W) × 3-
7
/8 (D)
in)
Weight 2.8 kg (6-
3
/16 lbs.)
Installation conditions Inside the control panel (indoor)
250(9-
7
/
8
)
155(6-
1
/
8
)
97.2(3-
7
/
8
)
266(10-
1
/
2
)
253.5(10) 5(
3
/
16
)
Unit: mm (in)
M-NET Terminal
block (M3.5)
LAN
LAN1 LAN2
Power source 100-240 VAC
Terminal block (M3.5)
Terminal block (to be used in the future when functions of the BAC-HD150 are upgraded.)