Master Lock 150000 BTU/Hr Electric Heater User Manual


 
7
101585
VENTILATION
OPERATION
Continued
Figure 6 - Flame-Out Control Reset
Button, 70,000 BTU/Hr Model
Figure 7 - Flame-Out Control Reset
Button, 100/150,000 BTU/Hr Models
WARNING
Follow the minimum fresh, outside air ventilation
requirements. If proper fresh, outside air ventilation is not
provided, carbon monoxide poisoning can occur. Provide
proper fresh, outside air ventilation before running heater.
Flame-Out
Control
Reset
Button
Flame-
Out
Control
Reset
Button
Provide a fresh air opening of at least three square feet (2800 square cm) for each
100,000 BTU/Hr rating. Provide extra fresh air if more heaters are being used.
Example:
A 150,000 BTU/Hr heater requires one of the following:
a two-car garage door raised six inches (15.24 cm)
a single-car garage door raised nine inches (22.86 cm)
two, thirty-inch (76.20 cm) windows raised twelve inches (30.48 cm)
WARNING
Review and understand the warnings in the
Safety
Information Section
, page 3. They are needed to safely
operate this heater. Follow all local codes when using this
heater.
To Start Heater
1. Follow all ventilation and safety information.
2. Fill fuel tank with kerosene or No. 1 fuel oil.
3. Attach fuel cap.
4. Plug power cord of heater into standard 230 volt/50 hertz, grounded (earthed)
outlet. Use an extension cord if needed. Use only a three-wire, grounded
(earthed) extension cord.
Extension Cord Wire Size Requirements
Up to 100 feet (30.5 meters) long, use 16 AWG (1.0 mm
2
) conductor
101 to 200 feet (30.6 to 61 meters) long, use 14 AWG (1.5 mm
2
) conductor
Heater will start when power cord is plugged into outlet. If not, push in flame-
out control reset button (see Figures 6 and 7).