LST BCnet216: 19" Smoke Alarm User Manual


 
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
BC216CE_DBL_LST_EN_0804.PDF • PAGE 4
ABuilding Safety. Building Security.
Specifi cations
Mains voltage 230VAC +10/-15%, 50Hz
Connection power 60VA
Output voltage typ. 28VDC
Output peak current max. 1.8A
Connection of external devices typ. 0.8A, site-specifi c
Own current consumption at 24V typ. 90mA (without optional componentries)
Ambient temperature -5°C to +50°C
Dimensions W × H × D 478 × 266 (6 height units) × 95 (mm)
Colour gray-white, RAL 9002
Weight without accumulator approx. 6kg
Approvals (EN 54-2, EN 54-4) VdS G201017
FT 14/147/3/99 (Austria)
By installing a Network Interface Module NIF5-1M in the
Fire Detection Control Panel BC216-1CE, the latter can
be integrated as BCnet sectional control panel with dis-
play and operating fi eld into a Fire Detection Control
Panel BCnet216. All sectional control panels are con-
nected with each other via a redundant high-security
network (the Global Security System network GSSnet).
Network Expansion of BC216-1CE
Permanent Connection
A variety of peripheral devices can be connected to the
fi re detection control panel Series BC216-1CE and to
the BCnet sectional control panel BC216-3CE:
• Fire brigade key safe
• Fire brigade control unit
• Acoustic and optical signaling devices
• External protocol printer
• Remote display and operating panels
• Remote indication unit
• Actuations
• Electronic monitoring system
• Transmitting device for the actuation of pagers via
ESPA protocol
• Modules for remote parameterisation and remote
maintenance via computer newtork, modem or GSM
connection
• Transmitter module for the transmission of messages
via SMS or e-mail
– and much more.
If required, the BC216-1CE or the BCnet216 can be
easily expanded to an extinguishing control panel ac-
cording to EN 12094-1. The extinguishing control panel
LC216-1 controls up to 8 fl ooding zones in one extin-
guishing system, without hardware redundancy. The
networked extinguishing control panel LCnet216 can
control up to 127 fl ooding zones in a maximum of 127
extinguishing systems.
The function of the extinguishing control panel is fully
integrated into the fi re detection control panels Series
BC216, a combined operation is therefore possible.
The LC216-1 and LCnet216 are certifi ed to EN 54-2,
EN 54-4, EN 12094-1 and VdS as a pure extinguishing
control panel and as a combined fi re detection and ex-
tinguishing control panel.
The networked extinguishing control panel LCnet216
can be optionally implemented with full hardware red-
undancy.
Extinguishing Control System