LST BCnet216: 19" Smoke Alarm User Manual


 
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
BC216CE_DBL_LST_EN_0804.PDF • PAGE 2
ABuilding Safety. Building Security.
Clear Concept
The compact control panel BC216-1CE and the BCnet
sectional control panel BC216-3CE are modularly desi-
gned control panels in 19“ slide-in technology. Depen-
ding on their confi guration, they provide the following
features:
• The Conventional Detector Interface GIF8-1 permits
the connection of automatic detectors and manual
call points in conventional technology as well as spe-
cial detectors with contact output. Individual detector
identifi cation can be achieved by means of an optio-
nal address module.
• Detectors and modules in ADM loop technology can
be connected to the Loop Interface LIF64-1. Depen-
ding on the parameterisation, either the Apollo/Disco-
very protocol or the System Sensor/200 protocol is
used to achieve bi-directional data transfer.
• Since the BCnet216 is compatible to LST fi re detec-
tion control panels of previous generations, the ex-
change or expansion of existing systems in conventi-
onal technology or ADM loop technology is possible.
The existing detector installation can be used without
changes.
• The optional Fire Brigade Interface FWI2-1 serves
for the connection of two independent transmitting
devices for a direct interconnection to a designated
alarm respondent (e.g., the fi re brigade) as well as
for the connection of a country-specifi c fi re brigade
control unit. By using the Fire Brigade Interface Addi-
tional Board FWZ2-1, a line supervision for both of the
transmitting devices is accomplished.
• Customizable outputs and logical combinations of
detectors and detector zones for the activation of
external controls and alarming devices facilitate ma-
ximum fl exibility. Thus, no additional expenses arise
for external relays, logic gates or timers. Thanks to
the wide range of parameterisation possibilities, indi-
vidual requirements even under the most diffi cult am-
bient conditions can be combined into a reasonable
fi re protection strategy.
• A monitored siren output and dry relay contacts for
alarm and fault are available by default.
• By integrating input and output modules on any positi-
on in the loop you can realize enablements or disable-
ments as well as control tasks in your system without
having to care for additional wires.
• The free combination of detectors and modules into
logic sectors allows for the joint operation of defi ned
parts of the system even beyond the limits of loops
or sectional control panels.
• The use of unshielded loop cables allows for cost-
saving and uncomplicated installation as well as for
the possibility of reusing the existing cabling.
• The LC text display (BC216-1CE) shows events with
the full information such as fl oor, room identifi cation
as well as date and time. This allows for quick and
targeted reaction in the event of a fi re as well as for
easy maintenance.
• An event memory allows for the display of the latest
500 events at any time (in the BCnet216 on the main
operating unit) with all required information. Thus, all
system conditions and user operations that occurred
are documented in a clearly laid out way.
• At a central processing board failure, the diversifi ed
redundancy concept ensures secure alarm recogniti-
on.
• The processor-monitored power supply ensures per-
manent surveillance and charging of the batteries.
This way, even during a mains power failure the un-
troubled and uninterrupted operation (for more than
72 hours depending on the design) is guaranteed.
• Three hierarchized authorization levels for operation
and parameterisation facilitate a high degree of secu-
rity against unauthorized access.
• The BC216-1CE control panel is easily operated
menu-driven via the display and operating fi eld. Clear
instructions on the display guide the user during com-
missioning, operation and maintenance.
• The parameter data of the BC216-1CE can be en-
tered either via the display and operating fi eld or, in
a more comfortable way, can be created by means
of PC software PARSOFT and loaded into the cont-
rol panel. The parameters of a BC216-3CE sectional
control panel are categorically set by means of PC
software PARSOFT. Thus, a quick and effi cient trans-
fer of the system confi guration into the control panel
is guaranteed.
• AUTO setup facilitates parameterisation when the
control panel is commissioned or expanded and thus
helps to save time.
The fl at case allows for easy mounting in virtually all
19“ pivoting frames, racks and housings. The case can
accommodate the function modules and the auxiliary
modules, apart from the central processing board. The
batteries can be placed either into the cabinet rack or
(up to 22Ah) into the optional battery bracket. Series
BC216 thus stands for modularity and easy expansion.
These products comply with all relevant standards of
EN 54 and are VdS-certifi ed. In addition, the products
also hold several country-specifi c approvals and certi-
fi cates. LST‘s high quality level is secured by a perma-
nently monitored quality management system certifi ed
by ISO 9001.